PULLFIRST[THE RECORD]
Permit / Golden Valley← Search
#GV123192

Mechanical

6100, Golden Valley

IssuedJan 7, 2025
StatusUnknown
Value$60,000
Inspections6
Scope of work

Remodel/Alteration, Additional supply ductwork, add return ducts, add 4 new ERV's and temp heat

Location context
Parcel2811821330006
Coordinates44.99249, -93.35665
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$615.23
Total paid$615.23
Timeline
ApprovedDec 11, 2024
IssuedJan 7, 2025
Inspection record
Inspections6
Passed6
Failed0
  1. Apr 22, 2025

    Balancing Report

    Completed

    InspectorBrian Stemwedel

    Compliant balkancing report entered into City's records
  2. Apr 22, 2025

    Final

    Completed

    InspectorBrian Stemwedel

    All work ISCWAP. duct insulation is SPF. all ducted returns
  3. Apr 9, 2025

    Duct Detector Test

    Completed

    InspectorBrian Stemwedel

    RTU's 1, 2, 3, And 4. verified control shutdown (individually as air handlers do not share a plenum) Comm with FACP verified. labeled RTU's with sharpie but contractor will label with permanent stickers
  4. Apr 8, 2025

    Rough-In

    Completed

    InspectorBrian Stemwedel

  5. Mar 18, 2025

    Duct Insulation

    Completed

    InspectorBrian Stemwedel

  6. Mar 7, 2025

    Rough-In

    Partial Approval

    InspectorBrian Stemwedel

    approved all ductwork with exception of rooftop ductwork and equip. locations, ERV's and associated intakes/ ex., and Type II hood (dishwasher). All ductwork was sealed with mastic as required

Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.