Location context
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$615.23
Total paid$615.23
Timeline
ApprovedDec 11, 2024
IssuedJan 7, 2025
Inspection record
Inspections6
Passed6
Failed0
- Apr 22, 2025
Balancing Report
CompletedInspectorBrian Stemwedel
Compliant balkancing report entered into City's records
- Apr 22, 2025
Final
CompletedInspectorBrian Stemwedel
All work ISCWAP. duct insulation is SPF. all ducted returns
- Apr 9, 2025
Duct Detector Test
CompletedInspectorBrian Stemwedel
RTU's 1, 2, 3, And 4. verified control shutdown (individually as air handlers do not share a plenum) Comm with FACP verified. labeled RTU's with sharpie but contractor will label with permanent stickers
- Apr 8, 2025
Rough-In
CompletedInspectorBrian Stemwedel
- Mar 18, 2025
Duct Insulation
CompletedInspectorBrian Stemwedel
- Mar 7, 2025
Rough-In
Partial ApprovalInspectorBrian Stemwedel
approved all ductwork with exception of rooftop ductwork and equip. locations, ERV's and associated intakes/ ex., and Type II hood (dishwasher). All ductwork was sealed with mastic as required
Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.