Lit Monument for Pace Dairy Foods
Disconnect existing sign by front entrance and connect new sign up from existing circuit that is there.
Disconnect old mcc gear (owner to demo out) add new 600 amp,(350 mcm X2) 480 v panel, new panel feeds new 75 KVA XFMR, XFMR feeds new 200 a, 120/208 panel. Relocate 4 old circuits from old mcc to other mcc’s in the plant.
Replace one for one xfmr’s : 4 - old 75kva’s for 4 - new 75 kva’s , 1 old 45kva for 1 new 45kva. Adding: 4 new - 75 kva’s from panels that are getting split up. New feeds from main switch gears room to these new xfmr’s and existing panels All xfmr’s are 480v primary and 120/208v secondary
Replace older MCC gear with new customer supplied gear. One for one replacement, no new loads were added. 3 phase, 480v, 600 amp.
Replace older DA skid with new customer supplied DA skid, one for one replacement. No new loads were added.