PULLFIRST[THE RECORD]
Permit / Minnetonka← Search
#MI284194

Building

10702 Red Circle Dr, Minnetonka

IssuedNov 6, 2024
StatusUnknown
Value$60,000,000
Inspections188
Scope of work

New, Full Permit: Market Rate Apartment Building w/ 269 units.

Location context
Parcel3611722310014
Coordinates44.89333, -93.41448
Loading map…
196 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedNov 1, 2024
IssuedNov 6, 2024
Inspection record
Inspections188
Passed146
Failed0
  1. Apr 21, 2026·7:00 AM - 8:00 AM

    Commercial Final

    scheduled

    InspectorMarshall Lind

  2. Apr 20, 2026·7:00 AM - 8:00 AM

    Commercial Final

    scheduled

    InspectorMarshall Lind

  3. Apr 16, 2026·7:00 AM - 8:00 AM

    Commercial Final

    scheduled

    InspectorMarshall Lind

  4. Apr 15, 2026·7:00 AM - 8:00 AM

    Commercial Final

    scheduled

    InspectorMarshall Lind

  5. Apr 14, 2026·1:30 PM - 3:00 PM

    Commercial Final

    scheduled

    InspectorMarshall Lind

  6. Apr 13, 2026·7:00 AM - 8:00 AM

    Commercial Final

    scheduled

    InspectorMarshall Lind

  7. Apr 8, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units: 482, 480, 478, 476, 474, 472, 470, 465, 463, 461, 459, 457, 455, 454, 453, 452, 451, 450, 449, 443, 441, CORRECTIONS: Need fire caulk in elect/data room, Carpet under fire rated doors
  8. Apr 8, 2026·7:00 AM - 8:00 AM

    Commercial Final

    scheduled

    InspectorMarshall Lind

  9. Apr 7, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units: 582, 580, 578, 576, 574, 572, 570, 565, 563, 561, 559, 557, 555, 554, 553, 552, 551, 550, 549, 543, 541, Storage, CORRECTIONS: 557 ceiling & insulation removed, Carpet under fire rated doors
  10. Apr 6, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units: 282, 280 278, 276, 274, 272, Storage ABC, 265, 263. 261, 259, 655, 654, 653, 652, 651, 650, 649, 641, CORRECTIONS: Data room needs fire caulk around pipes & wires, Common restrooms need pipe protection, Need to remove carpet under fire rated doors
  11. Apr 1, 2026

    Commercial Final

    CANCELLED APPOINTMENT

    InspectorMarshall Lind

    Per BN, Inspection canceled 8:20 4/1/26
  12. Mar 31, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Common area: Office suite 1-4, Leasing area & office 1-2, Work room lunch room, Conference room, Maintenance Office, Golf simulator, Club room, Fitness/work out room, Sauna, CORRECTIONS: All restrooms need pipe protection
  13. Mar 30, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 217, 219, 221, 223, 224, 225, 226, 227, 228, 230, 233, 236, 237, 238, 239, 240, Data room, Trash room, CORRECTIONS Unit 229 threshold to deckto high, Carpet under rated doors
  14. Mar 27, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    308, 313, 315, 317,320, 323, 326, 327, 328, 329, 330, 333, 336, 337, 338, 339, 340, Trash room CORRECTIONS: carpet under fire doors, 4 Storage units no name plates
  15. Mar 25, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Finals units 406, 408, 415, 423, 425, 427, 428, 429, 430, 432, 433, 434, 435, 436, 437, 438, 439, 440, Electrical room 4th floor, Elevator B, Trash room Corrections: Carpet under fire rated door in corridor
  16. Mar 24, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 508, 515, 523, 526, 527, 528, 529, 530, 532, 533, 534, 535, 536, 537, 538, 539, 540, 542 Storage, Trash room, CORRECTIONS 541 & 543 NOT READY, 536 ENTRY DOOR DOES NOT CLOSE, ELEVATOR B NEEDS SPRINKLER HEAD, FIRE RATED DOORS HAVE CARPET GOING UNDER THEM
  17. Mar 23, 2026

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    608, 615, 623, 627, 628, 629, 630, 6432, 633, 634, 635, 636, 637, 638, 639, 640 CORRECTIONS: Fire door Area B has carpet under doors, 649 needs window fall protection, Common area patio guard rail not 42" high/Check reach to shelve per ADA
  18. Jan 21, 2026

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation on Units 170, 157, 155, 154, 153, 152, 158, 158, 161, 163, 165 OK, Hallway between Units 180 - 158 & Hallway 158 - 165
  19. Jan 20, 2026

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation for units 180, 178, 176, 174, 172 CEILING CLOSED CELL INSULATION Unit 267 GENERATOR ROOM
  20. Jan 14, 2026

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire Blocking: Units missing FB around plumbing pipes 180, 178, 176., 174, 172, 170, 165, 163, 161, 159, 158, 157, 155, 154, 153 Unit 153 NEED TO COVER PIPE BREAKING FIRE RATED WALL & GAS LINE, UNIT 157 COVER PLUMB PIPE BREAKING FIRE WALL, UNIT 165 ROD & ELECTRICAL LINE COMING THROUGH CONCRETE CEILING, UNIT 170 NOT READY, UNIT 178 & 180 2 HOLES
  21. Dec 26, 2025

    Commercial Insulation

    CANCELLED APPOINTMENT

    InspectorMarshall Lind

    Showed up for inspection, No one on site, Text Doug & he said inspection is canceled
  22. Dec 23, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 100, 123 Mechanical room, 128, 130, 136, 137, 138, 139, 140, 141, 142, 143, 146, 148, 149, 150 OK
  23. Dec 18, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorBrian Stemwedel

    1st floor pre firestop inspection. no issues found Spoke with David re: Fire doors installed in firewalls at horizontal exits.
  24. Dec 16, 2025

    Meet Contractor

    SEE COMMENTS

    InspectorMarshall Lind

    Met with Doug about building finals /7 requirements to occupy the building
  25. Dec 15, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Screw patterns Units 280, 278, 276, 274, 272, 270, 268 ABC, 265, 263, 261, 265, 259, 255, 254, 253, 252, UNIT 268 ELECTRICAL NEEDS TO FIX SCREW SPACING
Show 163 earlier inspections
  1. Dec 12, 2025

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Final for Units 303, 305, 306, 307 Electrical Room, 309, 310 Storage, 319, 321, 322, 324, 325 CORRECTIONS UNITS 317, 320, 326 NEED TO ADJUST CLOSERS ON DOOR TO HALLWAY, UNIT 308 NO RAILING, UNIT 311 NEEDS GASKET ON MECHANICAL ROOM DOOR, UNITS 315 & 315 NOT READY, UNITS 323 NEEDS CO DETECTOR IN BEDROOM CHECK ON TYPE A REQUIREMENTS
  2. Dec 10, 2025

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    UNIT FINALS 401, 403, 405, 407 A Electrical, 407 BCD, 409, 410 Storage, 411, 413, 417, 419, 420, 421, 422, 424, 426 CORRECTIONS UNITS 406 NEEDS GASKET ON MECHANICAL ROOM, 408 NEEDS CO IN BEDROOM, 415 NEEDS CO IN BEDROOM & NEEDS TO FIX THRESHOLD ON MECHANICAL DOOR, 423 NEEDS CO IN BEDROOM, 425 NEEDS GASKET ON MECHANICAL DOOR
  3. Dec 9, 2025

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Final Units 624, 625, 626, 501, 503, 505, 507 Electrical room, 506, 509, 510 Storage, 511, 513, 517, 519, 520, 521, 522, 624, 526 UNITS THAT CO DETECTORS 623, 523, 515, 508 UNIT 526 NEEDS DOOR TO HALLWAY TO HAVE SPRINGS SET SO DOOR IS SELF CLOSER
  4. Dec 8, 2025

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 601, 603, 605, 606, 607 BC, 608, 610, 611, 613, 617, 619, 620, 621, 622 UNIT 615 HAS FURNACE IN BEDROOM/ NEED CO DETECTOR IN FURNACE ROOM & DOOR SEALED TIGHT
  5. Dec 5, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Screw patterns for units 380, 378, 376, 374, 372, 365, 363, 361, 350, 357, 355, 354, 353, 352 CORRECTIONS Unit 370
  6. Dec 3, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation for units 252, 253, 254, 255, 257 258ABC, 258 Data, Hallway between Units 280-258A,, Units 259, 261, 263, 265, Hallway between Units 258 Data - 258,
  7. Dec 2, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 270, 272, 274, 276, 278,,280 OK
  8. Dec 2, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Screw patters Units 482, 480, 478, 476, 474, 472, 470, 468, 465, 463, 461, 459, 457, 455, 454, 453, 452 OK
  9. Dec 1, 2025

    Commercial Wallboard

    CANCELLED APPOINTMENT

    InspectorMarshall Lind

    Texted at 6:21 12/1/25 don't need inspection David
  10. Nov 25, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Gypsum board in rim area only, Units 252, 253, 254, 255, 257, 259, 261, 263, 265, 270, 272, 274, 276, 278, 280
  11. Nov 24, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 353, 355, 357, 359, 361, 363, HALLWAY between Uni359-363
  12. Nov 21, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full Insulation Units 352, 354, Hallway from Units 368 Data - 352, Units 368 Data, 368 ABC, 370, 372, 374, 376, 378, 380, Hallway between Units 380 - 368 A, EXTERIOR walls Only 252, 253, 254, 255, 257, 259, 261, 263, 265, 270, 272, 274, 276, 278, 280
  13. Nov 19, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FULL WALL BOARD & SCREW PATTERNS Units 552, 553, 554, 555, 557, 559, 561, 565, 568, 570, 572, 574, 576, 578, 580 NEEDS SCREWS UNIT 563
  14. Nov 19, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire caulk NEEDS FIXING Units 259, 265 in 2 locations, UNITS INSULATED REMOVE INSULATION TO VERIFY FIRE CAULK Units 259, 261, 263
  15. Nov 18, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire Caulk for Units 255 & 272 OK
  16. Nov 18, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FULL INSULATION Units 461, 463, 465
  17. Nov 18, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Drywall in Rim Area Only, Units 352, 363, 354, 355, 357, 359, 361, 363, 365, 370, 372, 374, 376, 378, 380
  18. Nov 17, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire Caulk Units 252, 253, 254, 257, 268 ABC 268 Data, 270, 274, 276, 278, 280. MISSING FIRE CAULK Units 272, 255
  19. Nov 17, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation for Units 452, 5453, 454, 455, 457, 459, Hallway between units 452-457. Exterior walls insulation only Units 352, 353, 354, 355, 357, 359, 361, 363, 365, 370, 372, 374, 376, 378, 380
  20. Nov 14, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation for units 468, 470, 472,474, 476, 478, 480, NW hallway between units 474-480 Stuffed mineral wool for fire blocking in dead space where building comes together in units 353, 354, 368
  21. Nov 12, 2025

    Meet Contractor

    SEE COMMENTS

    InspectorBrian Stemwedel

    walking with David, noted fireblocking at floor level(s) in devising walls adjacent 352, 353, and 355, as well as shaft adjacent storage 363 were missing fireblocking at floor level. [718.2 MSBC]
  22. Nov 10, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorBrian Stemwedel

    lids blown FG Units: 552, 553, 554, and 555
  23. Nov 10, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorBrian Stemwedel

    above membrane gyp @ exterior walls. Units: 452, 454, 455, 457, 459, 461, 463, 465, 470, 472, 474, 476, 478, and 480
  24. Nov 7, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorBrian Stemwedel

    Rim insulation prior to gyp. Area 4C
  25. Nov 6, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorBrian Stemwedel

    Lids blown, units: 570, 572, 574, 576, 578, 580
  26. Nov 4, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorBrian Stemwedel

    Gyp cover at rim above membrane (exterior wall rated assembly) Units: 552, 553, 554, 555, 557, 559, 561, 563, 565, 570, 572, 574, 576, 578, and 580
  27. Nov 3, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    SCREW PATTERNS Units 652, 653, 654,655, 657, 661, 663, 665, 668 Data, 668 ABC, 670, 672, 674, 676, 678, 680
  28. Nov 3, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    EXTERIOR WALLS Units 552, 553, 554, 555, 557, 559, 561, 563, 565, 570, 572, 574, 576, 578, 580 Hallways between units 552-580 OK
  29. Oct 31, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    UNITS 578 & 580 NEED CORRECTIONS, Fire Caulk corrections OK, Units 576, 574, 555, 554, 561, 3rd & 4th Floor hallway on West side of bldg & West side of hall OK, 3rd & 4th Floor NW hallway on South wall of hallway OK
  30. Oct 31, 2025

    Commercial Wallboard

    SEE COMMENTS

    InspectorMarshall Lind

    Screw patterns 6th floor 1st layer in West hallway on exterior side OK, 6th floor NW hallway on South side of hallway wall OK
  31. Oct 29, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire Caulk Units 574, 572, 570, 568 Storage, 565, 557, 563, 561, 559, 553, 552, CORRECTIONS NEEDED UNITS 576, 574 Hallway, 555, 554, 561 Hallway, 565 Hallway
  32. Oct 28, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Exterior walls only, Units 652, 653, 654, 657, 659, 661, 663, 665, 670, 672, Interior hallway no poly between Units 652 - 668, Exterior hallway between Units 668A - 680 REMOVE 3 NAILS & SEAL
  33. Oct 27, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Exterior walls only Units 672, 674, 676, 678, 680
  34. Oct 24, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire caulk for Units 659, 676 & 659 hallway OK
  35. Oct 24, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Screw pattern for unit 227 OK
  36. Oct 23, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FIRE CAULK Units 651, 652, 654, 655, 657, 663, 665, 668, 668ABC, 670, 672, 674, 678, 680 NEED FIX UNITS 676, 654, 654 Hallway STAIRWAY E & D Grid on ceiling for fire rated assembly OK
  37. Oct 23, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Screw patterns Units 228, 229, 230, 233, 236, 237, 238, 239, 240, 241, 242 ABC, 242 Data, 249, 250 MISSING SCREWS Unit 227
  38. Oct 21, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 243, 249, 250, 251 & Corrections on 236 OK
  39. Oct 20, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 237, 238, 239, 240, 241, 242 ABC, 242 Data, 247, Elevator A, Hallway Unit 236 - 249, MISSING INSULATION 236
  40. Oct 17, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FULL INSULATION Units 227, 228, 229, 230, 233 HALLWAY & SHAFT in hallway Units 227 - 233
  41. Oct 15, 2025

    Commercial Wallboard

    CORRECTION NOTICE

    InspectorBrian Stemwedel

    In both stairways adjacent pass through (33) stack and full height exit enclosure, noted PVC plumbing penetrations in ceiling and shaft walls. this is not allowed per 713.8.1 MSBC, no exceptions apply to Code Section. Asked Doug to contact architect to find solution to issue and texted him photos and Code section (Doug- 612-382- 3729)
  42. Oct 14, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation in rim area Units #239, 240, 241, 243, 249, 250, 251 OK
  43. Oct 13, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation in Unit 333 OK
  44. Oct 13, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Rock in rim area Units 227, 228, 229, 230, 233 OK
  45. Oct 13, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire caulk in Units 229, 230, 231, 237, 238, 239, 421 OK, SCREW patterns in Units 430 & 443 OK
  46. Oct 10, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    INSULATION IN FLOOR JOIST AREA Units 227, 228, 230 233 NOT READY IN UNIT 229, SHEAR WALL & DEAD SPACE Units 228, 229, 333, MECHANICAL SHAFTS INSULATION ON NW & North side middle of hallway OK
  47. Oct 10, 2025

    Meet Contractor

    SEE COMMENTS

    InspectorBrian Stemwedel

    walked with Doug to review dead spaces and fireblocking. approved adjacent units 233/333 and stairway D
  48. Oct 8, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FIRE CAULK Units 227, 228, 236, 239, 240 242 ABC, 242 Data, 245, 249, 250, 251, CORRECTIONS Units 229, 230, 231, 237, 238 Hallway 239, 241
  49. Oct 7, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 339, 240, 241, 342 ABC, 343, 347 349, 350, 351, HALLWAY from units 336 - 351 OK
  50. Oct 3, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Screw patterns for Units 440 & 443 OK
  51. Oct 3, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 327, 328, 329, 330, UNIT 333 ceiling not blown until wall with void space is fixed, Hallway from units 328-333, Units full insulation 336, 337, 338
  52. Oct 3, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Pool room 123A Fire rated construction exterior wall OK, Interior steel studs OK
  53. Oct 2, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorBrian Stemwedel

    Framing in mech. shafts adjacent 68 stack and 55 stack. OK to insualte
  54. Oct 1, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    ROCK IN FLOOR JOISt AREA Units 327, 328, 329, 330, 333 SCREW PATTERN FULL WALLBOARD Units 427, 428, 429, 432, 433, 434, 435, 436, 437, 438, 439, 440, 441, 449, 450, 451 MISSING SCREWS 430, 443
  55. Sep 30, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Rock in Floor Joist Area Units 336, 337, 338, 339, 340, 341, 343, 349, 356, 357
  56. Sep 30, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Exterior wall insulation Units 327, 328, 329, 330, 333, 357
  57. Sep 29, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    INSULATION ON EXTERIOR WALLS Units 336, 337, 338, 339, 340, 341, 343, 350, MISSING INSULATION IN LIVING ROOM Unit 349
  58. Sep 25, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FIRE CAULK INSPECTION: Units 323, 329, 336, 337, 339, 349 HAVE CORRECTIONS, Units 328, 330, 333 DISCUSSING GAP BY WALL, 338, 340, 341, 342ABC, 343, 347, 350, 351 OK
  59. Sep 25, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation inspection Units 101 Club, 124, 126 OK
  60. Sep 24, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation: Units Elevator 445, 447, 449 450, 431 OK
  61. Sep 24, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorMarshall Lind

    TALKED TO DAVE & DOUG ABOUT VOID GOING DOWN FROM UNIT 333 & NEED ARCHITECT DETAIL
  62. Sep 23, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation for units 436, 437, 438, 439, 440, 441, 442, 443, Stairway A 4th floor
  63. Sep 22, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 427, 428, 430, 432, 433, 434, 435 OK, UNIT 429 NOT READY
  64. Sep 19, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Wallboard screw patterns NEED TO ADD SCREWS UNIT 535, 551. Units 527 - 550 OK Section B
  65. Sep 17, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Rock in rim area for units 427 - 451
  66. Sep 17, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    2nd floor exterior walls framing & insulation 205 Leasing room, Furred out wall & insulation 2nd floor next to 3 hr rated wall on South end OK, & 213 Package room OK
  67. Sep 16, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FLOOR JOIST RIM AREA Pre-rock Units 427 - 451
  68. Sep 15, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorChris Weaver

    ---STILL WAITING ON BRAUN REPORT REGARDING FIREWALL PENETRATIONS PREROCK INSULATION INSPECTION ALONG 4TH FLOOR PHASE 2 FIREWALL
  69. Sep 12, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FIRE CAULK Units 427, 428, 429, 430, 433, 434, 436, 437, 438, 439, 440, 443, 449, 450, 451, North elevator & trash room OK, FIX FIRE CAULK IN UNITS 432, 435
  70. Sep 10, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 542, 543, 549, 550, Trash Room, 551 HAS MOISTURE IN CEILING
  71. Sep 9, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation for units 534, 536, 537, 538, 539, 540, 541, Hallway from units 534 - 541 OK
  72. Sep 9, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    South end Common Area 1st floor, NEED TO FIRE CAULK ALL PENETRATIONS GOING UP THRU CONCRETE CEILING, Rest of framing OK
  73. Sep 8, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    South end 2nd floor common area, Steel studs, NEED FIRE CAULK ON COUPLE OF HOLES ON 3HR RATED WALL, All other framing OK
  74. Sep 8, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    FULL INSULATION Units 527, 528, 529, 530, 532, 533, 535, UNIT 534 NEEDS BEDROOM CEILING BLOWN INSULATION, HALLWAY from units 526 - 535 OK
  75. Sep 5, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * 5th floor rim gypsum in 5 units as noted on door cards
  76. Sep 4, 2025

    Commercial Insulation

    SEE COMMENTS

    InspectorChris Weaver

    ---QUESTIONED TAPE AND MUD ON TRUSS SPACE DRYWALL, SCREWS AND SEAMS, U305 WALL TYPE PER DOUG VIEWED PREROCK ON 5TH FLOOR PHASE B
  77. Sep 3, 2025

    Commercial Insulation

    SEE COMMENTS

    InspectorChris Weaver

    PREROCK INSULATION ON ENTIRETY OF 5TH FLOOR PHASE B OK PREVIOUS CORRECTIONS MADE
  78. Sep 2, 2025

    Commercial Insulation

    SEE COMMENTS

    InspectorChris Weaver

    VIEWED 3 UNITS ON 5TH FLOOR PHASE B FOR PREROCK INSULATION - ONLY 3 DONE VIEWED SCREW PATTERNS ON 6TH FLOOR PHASE B, NOTES ON CARDS
  79. Aug 29, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorMarshall Lind

    Fire Caulk: Missing needs fixing Units 527, 529, 535 water pipe, 537, 538 gas line, 541 plumbing drain pipe, 543 - 2 holes Fire Caulk OK Units 528, 530, 532, 533, 534, 536, 539, 540, 542, Trash, 549, 550, 551
  80. Aug 26, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 640 & 641 corrections OK
  81. Aug 22, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    HEADERS/SQUASH BLOCKING/ROOF TRUSSES 655, 657, 659, 661, 665, 666 ABC, 670, 672, 674, 676, 678, 680 OK
  82. Aug 22, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    UNITS 640, 642 Trash, 649, 650, 657, Common area room, CORRECTIONS 641
  83. Aug 20, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation Units 627, 628, 629, 630, 632, 634, 635, 636, 637, 638, 639 Compete
  84. Aug 19, 2025

    Commercial Framing

    CANCELLED APPOINTMENT

    InspectorMarshall Lind

    Per David, canceled inspection 6:06 am
  85. Aug 18, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire Caulk re-inspection, Units 628, 629, 630, 635, Common area are OK
  86. Aug 15, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire Caulk, CORRECTIONS FOR UNITS 628 Plumbing hole, 629 Bath fan wire 2 spots, 630 mechanical room 2 holes, 635 Water line on hallway wall, & COMMON AREA BY DOOR GOING TO EXTERIOR Units 627, 632, 633, 634, 636, 637, 638, 639, 640, 641, 644, Stairway A, 642, Trash room, 647, 649, 650, 657 OK
  87. Aug 14, 2025

    Commercial Insulation

    SEE COMMENTS

    InspectorChris Weaver

    HEADERS AND TRIMMERS ON 3RD FLOOR PHASE 2
  88. Aug 13, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    HEADERS/SQUASH BLOCKING & FLOOR JOIST Units 254, 255, 257, 270, 272, 274, 276, 278, 280, 268 Data/268ABC, 257, 261, 263, 265
  89. Aug 12, 2025

    Fire

    SEE COMMENTS

    InspectorLuke Berscheit

    Preliminary radio signal testing done only in phase 1 since it has drywall and windows (no doors yet). Building will need an emergency responder radio coverage system. Emailed job sup. to notify of the requirement.
  90. Aug 11, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Wall board & screw patterns 303, 306, 308 309, 313, 315 317, 319, 320, 321, 322, 323, 324, 325, 326 382 OK, RECHECK UNITS 305 & 311, Units 217, 219, 221, 223, 24, 225, 226, 282 OK
  91. Aug 8, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    STEEL FIRE PROOFING, Stairway C & South elevator shaft, Braun inspected & tested thickness
  92. Aug 6, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    HEADERS & ROOF TRUSSES Units 630, 632, 633, 634, 635, 636, 637, 638, 639, 640, 641, 642, 643, 644A, Elevator A, 642 Trash, 649, 650, 651, 652, 653
  93. Aug 5, 2025

    Commercial Insulation

    SEE COMMENTS

    InspectorChris Weaver

    WALKED ROOF
  94. Aug 4, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation for Units 217, 219, 221, 223, 224, 225, 226, 282 OK
  95. Aug 1, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Sheathing inspection Grid 2 Grid A - L, Sheathing inspection Grid F Grid 7 -12 Court yard side, Some pieces damaged between 5 & 6 floor, fix when applying house wrap
  96. Jul 31, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorChris Weaver

    5TH FLOOR PHASE B HEADERS AND TRIMMERS INSPECTION OK
  97. Jul 30, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation & vapor barrier in floor truss area Units 224, 225, 226
  98. Jul 30, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Wallboard in floor truss area Units 217, 219, 221, 223, 282
  99. Jul 29, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation in Units 324, 325, 326, Insulation & vapor barrier in floor truss area in Units 217, 219, 221, 223, 282
  100. Jul 28, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full insulation Units 311, 313, 315, 317, 319, 320, 321, 322, 323
  101. Jul 28, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Full rock Units 401, 403, 405, 406, 407 ABCD, 408, 409, 410, 411, 413, 415, 417, 419, 420, 421, 422, 423, 424, 425, 426
  102. Jul 25, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorDale Gronberg

    * Pre-insulation walk-thru of units 217-226 (OK)
  103. Jul 25, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * Units 303 - 308 (OK)
  104. Jul 24, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorChris Weaver

    PRELIMINARY FRAMING 4TH FLOOR PHASE B, HEADERS AND TRIMERS INSPECTION OK
  105. Jul 23, 2025

    Commercial Final

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Wall board in floor joist area up to unit 326 OK
  106. Jul 22, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation in floor joist area exterior walls Units 319, 320, 321, 322, 323, 324, 325, 326
  107. Jul 22, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Rock in floor joist area Units 303, 305, 306, 308, 209, 382
  108. Jul 21, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation in floor joist area Units 303, 305, 306, 308, 309, 311, 313, 315, 317, 382 OK
  109. Jul 18, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorMarshall Lind

    Fire caulk & framing OK for units 303, 305, 306, 308, 309, 310, 311, 313, 315, 320, 321, 322, 323, 324, 325, 326, 382 CORRECTIONS NEEDED UNITS 307 ELECTRICAL ROOM - HOLE IN FLOOR & AROUND ELECTRICAL SMURF TUBE, 317 BIG HOLE ON HALLWAY WALL, 319 HALLWAY WALL WATER LINE PIPE
  110. Jul 17, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorChris Weaver

    PHASE B MECHANICAL SHAFTS LOOKED AT
  111. Jul 16, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    1st layer rock units 413 & 415, Rock completed units 524 & 526 4th floor break off clips on 3hr wall OK
  112. Jul 15, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 419, 420, 421, 422, 423, 424, 425, 426 OK, Hallway to Unit 426 OK
  113. Jul 15, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 401, 403, 405 OK Units 501, 503, 505 506, 508, 509, 510, 511, 513, 515, 517, 519, 520, 521, 522, 523, 525, 582 All screw patterns OK
  114. Jul 14, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    2nd layer of rock in stairway C between floors 6/5 and 5/4
  115. Jul 14, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation OK for units 408, 410, 411, 413, 415, 417, 490 elevator lobby, Hallway from unit 408 - 417
  116. Jul 11, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation OK Units 401, 403, 405, 406, 407 ABCD, 409, Hallway from units 401 - 405
  117. Jul 10, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorChris Weaver

    HEADERS AND TRIMMERS CHECKED ON 4TH FLOOR PHASE 2 OK
  118. Jul 9, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Rock in rim area for units 401, 405, 406, 413 OK
  119. Jul 8, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation in rim area for units 417 - 426 OK
  120. Jul 8, 2025

    Commercial Wallboard

    CORRECTION NOTICE

    InspectorMarshall Lind

    UNITS 401 & 413 ROCK IN RIM AREA EXTENDS TO FAR DOWN GOES BELOW INSULATION & POLY, TALKED TO DOUG ON SITE
  121. Jul 7, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Pre rock insulation inspection in truss space for units 401, 403, 405, 406, 408, 409, 411, 413, 415, 482
  122. Jul 3, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorChris Weaver

    WALKED 4TH FLOOR PHASE A FOR FIRECAULK AND INSULATION BLESSING ---LOCATED MULTIPLE PENETRATIONS NOT CAULKED, INCLUDING TIE DOWNS AND ALARM ---FIREWALL HAS BEEN PENETRATED BY "SMURF TUBE" AND A LOT OF ELECTRICAL PENETRATIONS, REQUESTED DETAILS ---WET WALL ALONG FIRE WALL HAD MOST FIRE CLIPS RIPPED OUT FOR PLUMBING RE-WALK WITH ML
  123. Jul 2, 2025

    Meet Contractor

    SEE COMMENTS

    InspectorChris Weaver

    PHASE B 2ND FLOOR FRAMING OK MISSING MISC TRIMMERS, SQUASH BLOCKS, WILL BE READY FOR NEXT INSPECTION
  124. Jul 1, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Insulation OK in units 521, 523, 525, NEED INSULATION IN CEILING AREA IN UNITS 524, 526
  125. Jun 30, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Units 506, 508, 509, 510, 511, 513. 515, 517, 519, 520, 522 OK, 5th floor hallway from 501-522 OK
  126. Jun 27, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Exterior sheathing on East side and North East section of apartment, East side from East entrance North, North section from East wall to one section before jog in building to the North
  127. Jun 26, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * Units on 5th floor as noted on door cards (OK)
  128. Jun 25, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Exterior walls only Units 515-526 OK
  129. Jun 25, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Stairway C 1st layer on 6th floor only screw pattern OK Drywall screw patterns units 601-626 & 682 OK UNIT 515 NOT DONE NEED TO FINISH WALL BOARD WHEN TRASH CHUTE IS REMOVED Wallboard in rim area units 515-526
  130. Jun 24, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Pre-rock drywall in truss space for units 501-525 OK
  131. Jun 24, 2025

    Commercial Insulation

    CORRECTION NOTICE

    InspectorMarshall Lind

    WANTED INSULATION INSPECTION ON EXTERIOR WALLS FOR UNITS 515-526, NO VAPOR BARRIER AT THIS TIME, Text Dave not ready
  132. Jun 23, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Framing units 517, 519, 520, 522, 523, 524, 525, 526
  133. Jun 23, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    INSULATION EXTERIOR WALLS ONLY Units 501, 503, 505, 506, 508, 509, 511, 513, 515, 582
  134. Jun 20, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * Framing 5th floorunits as marked on door cards (OK) ***UNIT #582 NEEDS FIRECAULK AT 2 PLUMBING PENETRATIONS IN BATHROOM TOP PLATES*** ***UNIT 511 NEEDS STUD BELOW CUT TOP PLATE ON TRUSS BEARING WALL***
  135. Jun 18, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Fire blocking unit 682 OK SECTION B Roof sheathing,NEED TO REPLACE SHEATHING WITH FIRE RATED SHEATHING AT RATED WALL LOCATION Talked to Dave about access to mechanical units & needing ladders
  136. Jun 16, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Corrections on units 605, 608, 613, 615, 619, 621, 623 OK, Insulation in units 624, 625, 626 OK
  137. Jun 13, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorDale Gronberg

    ***AIR SPACE IN DOUBLE HEADERS MUST BE INSULATED TO AVOID CONDENSATION** * The following un its needs headers insulated 605,608,613,615,619,621,623 * Insuation in units 601,603,606,609,611,617,620,622 (OK) * Re-inspection on Monday. Take photos of 605 & 608 headers if drywalling today
  138. Jun 11, 2025

    Meet Contractor

    SEE COMMENTS

    InspectorKevin McDermott

    Amenity roof deck and phase 2 roof deck with parapet wall framing OK.
  139. Jun 10, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorChris Weaver

    SHEATHING PATTERS ON PHASE B REVIEWED OF 7 AND 7 DRAFT STOPPING DALE REQUESTED COMPLETED
  140. Jun 9, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorChris Weaver

    INSULATION UER PREROCK AREA IN DEMO UNITS OK
  141. Jun 6, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * Mock up Units 301 & 603 okay to insulate * 6TH FLOOR UNIT FRAMING: Okay as signed fon door cards * Add draftstopping at ceiling on common wall from Party room to dwelling * Unit 625 needs spray foam on rim
  142. Jun 4, 2025

    SOG/Vapor Barrier

    PARTIAL APPROVAL

    InspectorMarshall Lind

    North side & West side along parking garage, Need to seal around all bolts penetrating poly & all ripped areas. All pipes going thru poly sealed OK, talked to Doug on site
  143. Jun 2, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorChris Weaver

    ---SHAFT WALLS INSULATED AND DRYWALL 1ST LAYER, NO BLOCKING PRESENT AT ALL. SWH S4.4 INDICATES ALL SHAFT WALLS MUST BE BLOCKED
  144. May 30, 2025

    SOG/Vapor Barrier

    PARTIAL APPROVAL

    InspectorMarshall Lind

    North East side Phase B poly & seal OK
  145. May 30, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Phase A Mechanical shafts screw patterns floors 2 - 6 OK, Elevator shaft screw patterns floor 3, Elevator shaft floor 4 - 5 insulation OK, 6th floor elevator not ready
  146. May 28, 2025

    SOG/Vapor Barrier

    SEE COMMENTS

    InspectorChris Weaver

    LOOKED AT UNTAPED SHAFTS, 1ST LAYER
  147. May 27, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    PHASE A 3rd floor headers & squash blocking, Add squash blocking Unit 330, Braced wall screw pattern OK units 301 & 303, Met with Rylan
  148. May 21, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    4TH FLOOR PHASE A Headers & squash blocking Ok CORRIDOR SIDE FLOORS 1-6 EXTERIOR SHEATHING From Tunnel to )( stack, Replace broken pieces when installing house wrap
  149. May 19, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * 4TH FLOOR: 1st layer gypsum on Elevator A and trash chute shaft * 5TH FLOOR PHASE A: Exterior wall headers (OK) * Add a 3rd 2x10 (H7) over Unit #508 Patio Door with top bearing floor trusses
  150. May 12, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    6th floor headers on South end of building OK, 1. Need fire blocking between rated walls on elevator shaft on South end. 2. Need squash blocking in elevator shaft on 3rd level on North end. 3. Shaft on East end of floor 6 on South end of building needs another layer of rock All other shafts/elevators shafts/chutes fire rating OK on 2nd thru 6th on South end and floors 2nd & 3rd on North end.
  151. May 12, 2025

    Commercial Insulation

    PARTIAL APPROVAL

    InspectorMarshall Lind

    South end of building, Insulation and roofing OK, Need to finish installing boots over all penetrations and seal. At roof drain, will be applying closed cell spray foam insulation to the bottom of roof deck, 4 1/2 inches to get R value
  152. May 7, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorMarshall Lind

    Roofers have less than 10% done, Roofers not on site today due to wind, Will inspect Mon Morning
  153. Apr 30, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Exterior sheathing inspection before house wrap, South end South side wall only, Fixing sheathing that is damaged as they install house wrap, Need to seal wrap around deck brackets, window installer will be doing exterior taping. Need to nail parapet sheathing
  154. Apr 25, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    B section Level 2 level NE part, Stairway A Shaft & Stairway E rock & nailing, 01 Stack 3-5th floor ATS rods OK, 5th floor 515-517 shaft & 29 stack rock & nailing OK
  155. Apr 14, 2025

    Commercial Framing

    PARTIAL APPROVAL

    InspectorMarshall Lind

    South elevator fire rated assembly 4th floor W/insulation & house wrap, Shafts on South end fire rated assemblies, NEED TO FIX SHAFTS FIRE RATED WALLS WHERE FLOOR JOIST BUTT UP AGAINST
  156. Apr 9, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    South elevator 2nd floor 2 layers of rock, Shear walls South side level 3 OK
  157. Apr 9, 2025

    SOG/Vapor Barrier

    PARTIAL APPROVAL

    InspectorMarshall Lind

    SOG Vapor barrier South side Grid H.5 - Q, Grid 16 - 13
  158. Apr 8, 2025

    SOG/Vapor Barrier

    NOT READY

    InspectorMarshall Lind

    Call for re-inspection
  159. Apr 8, 2025

    Commercial Wallboard

    PARTIAL APPROVAL

    InspectorMarshall Lind

    South elevator 2nd floor wall rating OK, South rated fire wall fire clips OK
  160. Apr 1, 2025

    SOG/Vapor Barrier

    NOT READY

    InspectorMarshall Lind

    Due to weather, Dave stated he called Beth & canceled
  161. Mar 31, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorMarshall Lind

    Met with head framer
  162. Mar 28, 2025

    SOG/Vapor Barrier

    PARTIAL APPROVAL

    InspectorMarshall Lind

    Lowest floor Grid J.6 - D, Grid 12 - 16
  163. Mar 18, 2025

    Commercial Framing

    SEE COMMENTS

    InspectorMarshall Lind

    Pre construction meeting with Dave, Dave will be main contact for inspections, 847-845-6206

Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.