#MG396216Mechanical
13601 Grove Dr N, Maple Grove
IssuedOct 10, 2024
StatusUnknown
Value$15,900
Inspections9
Scope of work
Remodel, Install type 1 hood, exhaust fans, Make up air unit, ductwork, roof tops
Location context
Parcel2211922240012
Coordinates45.10403, -93.45329
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedOct 9, 2024
IssuedOct 10, 2024
Inspection record
Inspections9
Passed1
Failed0
- Mar 12, 2025
Final
PassInspectorDoug Becker
- Mar 11, 2025
Final
Not ReadyInspectorDoug Becker
capture test failed
- Mar 5, 2025
Final
Partial InspectionInspectorDoug Becker
still need capture and containment test to pass, need installation instructions on new larger table top cooker, and need full balance report
- Feb 27, 2025
Final
Partial InspectionInspectorDoug Becker
need paper work on new table top electric griils, need paper work on new heat load, capture and containment, and vestibule
- Feb 26, 2025
Final
Partial InspectionInspectorDoug Becker
dishwasher exhaust duct
- Feb 19, 2025
Final
Partial InspectionInspectorSteve Lano
Type 2 hood vent for dishwasher not sealed. Vestibule to energy code 6.4.3.9. Table top grills not what is specified on engineeredd plans.
- Feb 18, 2025
Rough-In
Partial InspectionInspectorDoug Becker
Grease duct ok but need to test dishwasher duct. no plans or permit onsite advised nent time no plans no inspection
- Jan 28, 2025
Rough-In
Partial InspectionInspectorDoug Becker
grease duct water test -right exhaust is ok left still has a leak at first weld from the top will recheck at water test for dishwasher exhaust
- Jan 14, 2025
Rough-In
Not ReadyInspectorCaleb Hansen
Grease duct