Permit / Ramsey← Search
#RA058389Fire
7895 Sunwood Dr NW, Ramsey
IssuedJun 21, 2024
StatusUnknown
Value$78,000
Inspections4
Scope of work
New Commercial, Commercial
Location context
Fees & payments
Total fees$1,424.59
Timeline
ApprovedJun 20, 2024
IssuedJun 21, 2024
Inspection record
Inspections4
Passed1
Failed0
- Jan 15, 2026
Alarm Test
PassInspectorChris Weiss
- Oct 15, 2025
Alarm Test
Orders IssuedInspectorChris Weiss
Most of the previous issues have not been corrected
- Sep 16, 2025
Alarm Test
Orders IssuedInspectorChris Weiss
Hearing impaired Rooms, 410,426, 320,313, 21,212,201,106, 103 Strobes did not activate when smoke detector activated. NO carbon monoxide detection is provided in each room lawfully used for sleeping purposes.
- Sep 4, 2025
Alarm Test
Orders IssuedInspectorChris Weiss
Smoke detectors in rooms were installed to low, notifications were delayed, fire doors for elevators did not latch. strobes missing in ADA rooms. Room detectors active building alarm system.
Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.