PULLFIRST[THE RECORD]
Permit / Ramsey← Search
#RA058389

Fire

7895 Sunwood Dr NW, Ramsey

IssuedJun 21, 2024
StatusUnknown
Value$78,000
Inspections4
Scope of work

New Commercial, Commercial

Location context
Fees & payments
Total fees$1,424.59
Timeline
ApprovedJun 20, 2024
IssuedJun 21, 2024
Inspection record
Inspections4
Passed1
Failed0
  1. Jan 15, 2026

    Alarm Test

    Pass

    InspectorChris Weiss

  2. Oct 15, 2025

    Alarm Test

    Orders Issued

    InspectorChris Weiss

    Most of the previous issues have not been corrected
  3. Sep 16, 2025

    Alarm Test

    Orders Issued

    InspectorChris Weiss

    Hearing impaired Rooms, 410,426, 320,313, 21,212,201,106, 103 Strobes did not activate when smoke detector activated. NO carbon monoxide detection is provided in each room lawfully used for sleeping purposes.
  4. Sep 4, 2025

    Alarm Test

    Orders Issued

    InspectorChris Weiss

    Smoke detectors in rooms were installed to low, notifications were delayed, fire doors for elevators did not latch. strobes missing in ADA rooms. Room detectors active building alarm system.