Permit / Ramsey← Search
#RA056135Building
7895 Sunwood Dr NW, Ramsey
IssuedJul 9, 2024
StatusUnknown
Value$1,824,700
Inspections14
Scope of work
New, Interior
Location context
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedJul 9, 2024
IssuedJul 9, 2024
Inspection record
Inspections14
Passed8
Failed0
- Jan 15, 2026
Final Building
PassInspectorThomas Knight
All Corrections have been completed.
- Sep 18, 2025
Final Building
Partial PassInspectorThomas Knight
All Guest rooms can be occupied Pool Room is not to be used. 1. Seal all exterior penetrations and areas where exterior finish changes materials 2. HVAC Must pass/submit Balance report 3. Proper devices in ADA Hearing impaired rooms 4. Door sweeps are missing on 1st floor guest room doors 5. Electrical Final Must pass 6. Post Address Numbers in accordance with City Code 7. Provide Paperwork required by Fire inspector/pass fire inspection. 8. All Pool areas are not complete and cannot be used.
- Sep 18, 2025
Fire Wall
PassInspectorThomas Knight
All penetrations have been completed special inspections report has been received, Engineering provided for horizontal Fire Assembly
- Sep 8, 2025
Final Building
Partial PassInspectorThomas Knight
1. Adjust door on 408 2. Repair smoke seal on west stairway 4 door 3. Patch Sprinkler Escutcheon in 401,413,417,103,105 4. Gypcrete and finish flooring in Linen Chute access room on 4,3,2 5. Missing Fresh air vent in 329 6. Missing Ceiling tiles on all floors. 7. Fire caulk lineset and thermostat wire in housekeeping on floor 3 8. Unit 323 is missing Bath fan cover 9. Fix vertical Handicap bar location (39-41) off back wall in Handicap units 10. Remove paint from all door frame to check Fire rating of door frames 11. Patch hole in walls 220, 205,209,211,213,221,101,102,103,107,110, 106 12. Adjust Door closer hinges in 212 for adjoining room door 13. Install Ptac covers in 223 14. Adjust doors for 218, 229 and 231 15. Seal bathroom tile in unit 101 16. Fix Broken Tiles in 110 17. Missing Faucet in 110 18. Missing Trap Warp in breakroom sink 19. Guest Laundry is missing door/glass in doors and handles. This area not to be used. 20. Adjust Closers for Sprinkler room 21. Adjust closers in Electrical Room 22. Fire tape above door in Electrical room 23. Fire tape above Mini split in Sprinkler room 24. Manometer test required for exterior gas lines for grills and fire pit 25. Test Emergency shutoff for Gas for grills and Fire pit 26. Seal all exterior penetrations and areas where exterior finish changes materials 27. All Automatic doors must be operable 28. Sanitize Eye wash stations 29. Laundry Chute must have self closing door 30. Laundry chute room smoke detector at wrong height 31. HVAC Must pass/submit Balance report 32. Submit Report from Fire engineer to the City for Horizontal Fire Assemblies 33. Fire alarm system must be operational 34. Fire Caulk all penetrations in Data room 35. All Pool areas are not complete and Cannot be used. 36. Safety Glazing required in all hazardous locations
- Sep 5, 2025
Final Building
Partial PassInspectorThomas Knight
OK to Issue temp C of O **** Occupancy limited to hotel Hilton employees/affiliates on 1st Floor Only. Pool area and Laundry Facilities must be locked and are not to be used***** ****24 hour Fire Watch required for all floors during occupancy until approved by city******* Provide Acceptable Fire Engineer report for Horizontal Fire Assemblies Provide Proof of passing Elevator inspection from the state of MN Submit Balance report Final HVAC Inspection Verify Heat and AC in all guest rooms and Occupancy sensors Verify all exhaust fans are operating Verify Heat and AC are working in common areas and back of house rooms Move Smoke detectors to approved locations and Patch any holes in the walls Tempered Glazing in all safety locations Proper fire doors installed in all locations Verify Emergency lighting and exit lights Strobes installed and operational in all hearing impaired rooms All Penetrations sealed on exterior Ensure all covers or trap wraps are installed for drains All handicap signage installed to code All toilets sealed at floor Ensure all door closers are operating and doors latching All Pool areas and bathrooms must be completed.
- Jul 24, 2025
Fire Wall
Orders IssuedInspectorThomas Knight
Looked at Fire penetrations on all floors. All floors had corrections. Special inspector to verify corrections and notify building department when ceiling tiles can be installed.
- Jul 15, 2025
Final Building
Orders IssuedInspectorThomas Knight
Inspection for emergency lighting and exit lighting only. Exterior emergency lights not working over exterior doors. Multiple missing or not working exit lights. Multiple emergency lights were not operational. Missing emergency exit light next to kitchen in hallway. Generator was operational at time of inspection.
- Jun 20, 2025
Final Building
Orders IssuedInspectorThomas Knight
Seal all exterior penetrations seal where stone meets other finishes. Correct all issues with Handicap accessibility complete all plumbing work and inspections complete all emergency exit lighting and signage Roof drains cannot drain onto sidewalk Electrical must be completed and all inspection complete Mechanical must be complete,operational, and all inspections complete Missing trim around outside of Ptac units Missing door thresholds Missing door hardware Missing fire extinguishers Safety Glazing required on hallway windows on west side This is not a complete list since so many items remain outstanding. Full Final inspections will still be needed upon substantial completion of the building
- Feb 13, 2025
Fire Wall
Orders IssuedInspectorThomas Knight
penetrations above dropped ceiling that go into new fire partition walls on the units that had the rain leader issue must be fire caulked per code
- Jan 13, 2025
Fire Wall
Orders IssuedInspectorThomas Knight
Cavities in unit 223 do not have Proper depth of gypcrete. under all shower pans on floor 2 gypcrete is not min 3/4"
- Jan 8, 2025
Fire Wall
Orders IssuedInspectorThomas Knight
Units with Roof drains in shower cavities have created a shaft. Rated shaft or repair by licensed design professional required
- Oct 30, 2024
Topsoil
Partial PassInspectorJake Hoel
Per email from Jake Hoel on 10/30/24; partial pass - west of building partial pass due to equipment and containers are
- Oct 10, 2024
Topsoil
Not approvedInspectorAaron Madsen
Per email from Aaron Madsen on 10/10/24; failed because it's only half done. And sod is on some.
- Sep 26, 2024
Topsoil
Partial PassInspectorJake Hoel
Per email from Jake Hoel on 9/26/24; partial pass. North side of the building is good, however topsoil is needed on south side and west of the parking lot.