PULLFIRST[THE RECORD]
Permit / Ramsey← Search
#RA060542

Fire

6840 Highway, Ramsey

IssuedJan 3, 2025
StatusUnknown
Value$2,609
Inspections3
Scope of work

Commercial Revision, Commercial

Location context
Parcel343225210096
Coordinates45.22371, -93.44097
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$84.55
Timeline
ApprovedJan 3, 2025
IssuedJan 3, 2025
Inspection record
Inspections3
Passed3
Failed0
  1. Jun 13, 2025

    Final

    Pass

    InspectorChris Weiss

    Alarm for alarm notification was just over 1 minute from the time alarm was activated until fire department was notified.
  2. Jun 10, 2025

    Final

    Partial Pass

    InspectorChris Weiss

    Took extremely long for alarm company to receive and dispatch fire. First attempt stopped after 20 minutes. Change made, second attempt took over 6 minutes.
  3. Feb 5, 2025

    Final

    Partial Pass

    InspectorChris Weiss

    Batteries were installed in 2018, breaker for Fire Alarm panel not red, and there was no distinction form a fire alarm or water flow. Test report showed no difference between a water flow alarm and smoke detector activation.

Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.