Permit / Ramsey← Search
#RA060713Building
7007 168th La NW, Ramsey
IssuedFeb 26, 2025
StatusUnknown
Value$325,893
Inspections13
Scope of work
Repair
Location context
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedFeb 26, 2025
IssuedFeb 26, 2025
Inspection record
Inspections13
Passed8
Failed0
- Jun 5, 2025
Final Building
Orders IssuedInspectorDean Becker
All will pass once a copy of the Helical Pier report has been received, reviewed, and approved ( from 4/2/2025 footing inspection). dean@rumrivercc.com.
- Jun 5, 2025
Footing
PassInspectorDean Becker
Received, reviewed, and approved the helical report.
- Jun 2, 2025
Lath
PassInspectorDean Becker
- Apr 30, 2025
Insulation
PassInspectorDean Becker
- Apr 25, 2025
Framing/Sheathing /Rim Joist
PassInspectorEric Hoffman
All corrections from 4/10/25 completed. Updated plans on file for narrow wall details on garage bays.
- Apr 10, 2025
Framing/Sheathing /Rim Joist
Orders IssuedInspectorDean Becker
(4) Garage brace wall hold downs need screws on 2 of 4 locations. (6) Need portal frame detail clarified. Build to plan (8) Needs CS16 coil straps at ends of upper level wall facing street. (the two adjacent walls on sides are good). May need additional engineering for alternative.
- Apr 10, 2025
Insulation
Partial PassInspectorDean Becker
House Only - no garage insulation installed at time of inspection.
- Apr 7, 2025
Framing/Sheathing /Rim Joist
Orders IssuedInspectorEric Hoffman
(3) Needs C10 Truss fix inspected (All fixes on file now) (4) Garage brace wall hold downs need screws on 2 of 4 locations. (6) Need portal frame detail clarified. Build to plan (8) Needs CS16 coil straps at ends of upper level wall facing street. (the two adjacent walls on sides are good). May need additional engineering for alternative. ***Gave ok to insulate house and spray foam garage rim and HVAC trunk, check for C10 fix at insulation, they will need to leave the garage front uncovered as the portal framing issue need to be corrected***
- Apr 7, 2025
Footing
Partial PassInspectorEric Hoffman
Affidavit on file for core filling per plan
- Apr 7, 2025
Window/Door Installation
PassInspectorEric Hoffman
Rough -in of windows / doors ok. Review completed installation at final
- Apr 7, 2025
Water-Resistive Barrier
PassInspectorEric Hoffman
Contractor ensures window facing street will have the seams taped.
- Apr 2, 2025
Footing
NotesInspectorEric Hoffman
Needs helical report for final Needs pictures of core filled block at PSL post in garage
- Apr 2, 2025
Framing/Sheathing /Rim Joist
Orders IssuedInspectorEric Hoffman
(1) Needs WRB and Window/Door Inspections to pass before drywall and siding. Ran out of time at framing. (2) Needs Truss Fixes for file x 4 trusses (fixes for 3 of 4 were verified) (3) Needs C10 Truss fix inspected (1 of the 4) (4) Garage brace wall hold downs need screws on 2 of 4 locations. (5) Need plan update for garage 3-ply beam alternative. Girder truss observed. (6) Need portal frame detail clarified. No hold-downs observed. Block construction. (7) Need pictures of core filled garage block under PSL post in garage. (8) Needs CS16 coil straps at ends of upper level wall facing street. (the two adjacent walls on sides are good)