Building

1637 Kelly Dr, Golden Valley

IssuedMar 6, 2025
StatusUnknown
Value$300,000
Inspections35
Scope of work

New, New construction of a 1-story ADU and garage.

Location context
Parcel2911821310054
Coordinates44.99708, -93.37288
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$1,468.03
Total paid$1,468.03
Timeline
ApprovedMar 6, 2025
IssuedMar 6, 2025
Inspection record
Inspections35
Passed24
Failed0
  1. Oct 15, 2025

    Blower Door Test

    Completed

    InspectorDan Anderson

  2. Oct 13, 2025

    Energy Code-Lighting Schedule Form

    Completed

    InspectorDan Anderson

    Bret confirmed all lights are LED
  3. Oct 13, 2025

    As-Built Survey

    Completed

    InspectorDan Anderson

  4. Oct 6, 2025

    Other - Smoke & Carbon Alarm at Time of Final

    Completed

    InspectorBret Eggers

  5. Oct 6, 2025

    Radon Control

    Completed

    InspectorBret Eggers

  6. Oct 6, 2025

    Submit Pictures of House Wrap

    Completed

    InspectorBret Eggers

  7. Oct 6, 2025

    Verify Electrical Final

    Completed

    InspectorBret Eggers

  8. Oct 6, 2025

    Final

    Need Correction

    InspectorBret Eggers

    All corrections from 9/2 completed. Current outstanding correction- Roof issues not addressed
  9. Sep 2, 2025

    Other-Slab On-Grade Perimeter Insulation

    Completed

    InspectorMike Lockman

    Insulation is integral with the forms used for footings/foundation
  10. Sep 2, 2025

    Soil Test - Req`d Before Footing

    Completed

    InspectorMike Lockman

    Geo report loaded into Pdox. Dated 7-26-2024
  11. Sep 2, 2025

    Insulation

    Completed

    InspectorMike Lockman

    SIP panels installed for exterior walls and roof. R-21.1 @ walls and R-49 @ roof assembly per manufacturer
  12. Sep 2, 2025

    Final

    Need Correction

    InspectorMike Lockman

    1. Electrical final had not yet been completed at time of final inspection 2. Anti-tip device not installed on range as required by manufacturer 3. Hole in garage ceiling for electrical repair has not been repaired 4. Radon venting has not been completed and terminated thru roof 5. Relief piping not completed on water heater or boiler 6. House address not posted on exterior of home 7. Floor shall be sealed at shower/floor intersection ( hallway bathroom ) 8. CO alarm required outside of 2nd bedroom ( back side of home ) 9. Screening require for outdoor AC condenser units
  13. Sep 2, 2025

    Other - Smoke & Carbon Alarm at Time of Final

    Need Correction

    InspectorMike Lockman

    Missing CO alarm outside of 2nd bedroom on back side of home
  14. Sep 2, 2025

    Submit Pictures of House Wrap

    Not Approved

    InspectorMike Lockman

    HW photos not provided by contractor at time of final inspection
  15. Sep 2, 2025

    Submit Pictures of Ice & Water Shield

    Not Approved

    InspectorMike Lockman

    Photos not provided by contractor at time of final inspection or inspection called in for
  16. Sep 2, 2025

    Verify Electrical Final

    Not Ready

    InspectorMike Lockman

    Electrical final has not been completed as of date of final inspection
  17. Sep 2, 2025

    Energy Code-Lighting Schedule Form

    Not Ready

    InspectorMike Lockman

    Report not provided by contractor as of time of inspection
  18. Sep 2, 2025

    As-Built Survey

    Not Ready

    InspectorMike Lockman

    As-Built survey has not been provided by contractor at time of inspection
  19. Sep 2, 2025

    Blower Door Test

    Not Ready

    InspectorMike Lockman

    Report has not been provided by contractor at time of inspection
  20. Sep 2, 2025

    Drain Tile

    Not Required

    InspectorMike Lockman

    Slab on grade construction - DT not required
  21. Aug 29, 2025

    Final

    Completed in Future.

    InspectorMike Lockman

    Verify the installation of the above grade radon pipe and a down tube at the relief valve on the water heater. Close out plbg permit GV124587 if completed
  22. May 20, 2025

    Framing

    Completed

    InspectorMike Lockman

    SIP installed substantially compliant w/ engineered drawings. Verified compliant support at point loads below structural beams. Electrical RI sticker dated 5/15/25
  23. May 19, 2025

    Framing

    Cancelled Appointment

    InspectorMike Lockman

    Cancelled by contractor. Will reschedule
  24. Apr 14, 2025

    Framing

    Completed

    InspectorBret Eggers

  25. Apr 8, 2025

    Insulation - Under Slab

    Completed

    InspectorMike Lockman

    2" R10 foam insulation installed under entire slab and taped at seams
Show 10 earlier inspections
  1. Apr 8, 2025

    Foundation Insulation

    Completed

    InspectorMike Lockman

    R10 minimum insulation installed on interior and exterior of foundation. Slab on grade.
  2. Apr 8, 2025

    Floor Slab

    Completed

    InspectorMike Lockman

  3. Apr 8, 2025

    Foundation Waterproofing

    Not Required

    InspectorMike Lockman

    Slab on grade system. Balanced fill at foundation
  4. Apr 8, 2025

    Radon Control

    Partial Approval

    InspectorMike Lockman

    6 mil vapor barrier installed. Taped at seams and at all penetrations
  5. Apr 3, 2025

    Foundation Insulation

    Cancelled Appointment

    InspectorMike Lockman

    Inspection cancelled by contractor
  6. Apr 3, 2025

    Site - Verify Setbacks at Footing Inspection

    Completed

    InspectorMike Lockman

  7. Apr 1, 2025

    Footing

    Completed

    InspectorMike Lockman

    Footings are SCWAP and engineering. Slab on grade w/ shallow footing system per ASCE-32
  8. Apr 1, 2025

    Footing - Reinforcing

    Completed

    InspectorMike Lockman

    (2) #4 bar at both top and bottom. SCWAP
  9. Apr 1, 2025

    Radon Control

    Partial Approval

    InspectorMike Lockman

    3" Perforated piping below slab. Compliant w/ Mn IRC requirements
  10. Mar 28, 2025

    Radon Control

    Not Approved

    InspectorMike Lockman

    The underground radon piping failed to meet the requirements of Mn Rule 1303.2402 in the Mn Residential Building Code. Re-inspection is required