Permit / Golden Valley← Search
#GV124160Building
7155 Medicine Lake Rd, Golden Valley
IssuedApr 8, 2025
StatusUnknown
Value$125,000
Inspections16
Scope of work
Remodel/Alteration, WAREHOUSE/OFFICE-Build out of Old Service Station, no additional work in the warehouse building,
Location context
Parcel2911821210056
Coordinates45.00727, -93.37144
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$785.53
Total paid$785.53
Timeline
ApprovedApr 2, 2025
IssuedApr 8, 2025
Inspection record
Inspections16
Passed14
Failed0
- Sep 12, 2025
Verify Fire Final
CompletedInspectorDan Anderson
approved by KJ 9/11/25
- Aug 20, 2025
Verify Fire Final
Need CorrectionInspectorBrian Stemwedel
Visual alarm identified in FA Plan review needs to be installed in bathroom in new office space (Public Area) [907.5.2.3.1 Public use areas and common use areas.] Provide a visible alarm in bathroom (Public use area) Visible alarm notification appliances shall be provided in public use areas and common use areas. It does not appear you have 20% spare capacity; therefore, the exception does not apply.
- Aug 11, 2025
Final
CompletedInspectorBrian Stemwedel
Contractor sent picture of installed emergency light at exterior. ok to approve and close permit upon verification of electrical final and fire final
- Jul 17, 2025
Final
Completed in Future.InspectorBrian Stemwedel
Emergency lighting @ exit discharge [1008.3.2(5) MSBC] Verify Fire final Verify electrical final
- Jul 9, 2025
Flat Roof/Tear-Off
CompletedInspectorBrian Stemwedel
- Jul 9, 2025
Insulation
CompletedInspectorBrian Stemwedel
DC 315 intumescent applied over SPF in exterior wall where exposed in plenum. Installer Statement entered into City archive
- Jul 9, 2025
Insulation-Roof Insulation
CompletedInspectorBrian Stemwedel
- Jun 12, 2025
Framing
CompletedInspectorBret Eggers
- Jun 12, 2025
Framing-Above Ceiling
CompletedInspectorBret Eggers
- Jun 12, 2025
Insulation
Completed in Future.InspectorBret Eggers
Complete when Intumesecnt report approved
- May 23, 2025
Floor Slab
CompletedInspectorBrian Stemwedel
slab connecting office to building
- May 23, 2025
Footing
CompletedInspectorBrian Stemwedel
grade beam connecting buildings per agreement
- May 23, 2025
Insulation - EIFS /Flashing details
CompletedInspectorBrian Stemwedel
details at infills
- May 23, 2025
Submit Pictures of House Wrap
CompletedInspectorBrian Stemwedel
sealed at perimeter against ex. EIFS
- May 23, 2025
Wall Reinf. inspect @ 4` lift prior to grout
Not RequiredInspectorBrian Stemwedel
changed to grade beam connection buildings 5' apart. supported each end on ex. foundation(s)
- Apr 29, 2025
Other
CompletedInspectorBrian Stemwedel
Met with design/ build team on site. went over exterior envelope/ havc concerns and went over expectations for Code requirements relating to energy Code. informed permit holder that changes to the design would require plan revisions for our records