PULLFIRST[THE RECORD]
Permit / Golden Valley← Search
#GV126378

Building

123 Ottawa Ave N, Golden Valley

IssuedJul 28, 2025
StatusUnknown
Value$48,351
Inspections4
Scope of work

Remodel/Alteration, SCHOOL/Remodel of maintenance offices

Location context
Parcel1902924340019
Coordinates44.97911, -93.34059
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$442.36
Total paid$442.36
Timeline
ApprovedJul 15, 2025
IssuedJul 28, 2025
Inspection record
Inspections4
Passed3
Failed0
  1. Aug 29, 2025

    Final

    Need Correction

    InspectorBrian Stemwedel

    occupancy change from S1/S2 to B (new milti use Room 101, storage room 100, and offices 102, 103) require 1 hour separation [ table 508.4 MSBC]. Fire doors between S occ. and B occ need to be installed or restored, did not see required label, so verify rating per Table 716.1(2) which is 45 min -remove hold open devices attached to fire doors and verify doors self close and latch as required. Separation also required between E occ (corridor) and new office/ multi use. rated doors are installed but did not operate properly. coordinator was not working. verify doors self close and latch and coordinators hold active panel open until side panel closes (verify positive latching and listed fire exit hdwr installed.)
  2. Aug 22, 2025

    Wall Reinforcing - Lintel Locations

    Completed

    InspectorMike Lockman

    did not call for reinforcing steel, just grout
  3. Aug 22, 2025

    Wall Reinforcing - Grout

    Completed

    InspectorMike Lockman

    Window location per plans in corridor
  4. Aug 8, 2025

    Framing

    Completed

    InspectorMike Lockman

    NS framing installed SCWAP. Opening in CMU w/ lintel has not been completed at the time of this inspection. Verified 45 min fire rated glass in window per plans

Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.