PULLFIRST[THE RECORD]
Permit / Crystal← Search
#CY089257

Building

4741 Welcome Ave N, Crystal

IssuedFeb 21, 2025
StatusUnknown
Value$184,680
Inspections6
Scope of work

New, Basement finish for 4 unit

Location context
Parcel0911821310014
Coordinates45.04076, -93.35150
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$2,537.69
Inspection record
Inspections6
Passed2
Failed4
  1. Jan 27, 2026

    Final - New Construction

    Fails to comply

    InspectorJeni Taylor

    Unit A Missing hardwired smoke detector in lower level bedroom. Missing hardwired smoke/CO detector in lower level hallway. Missing hardware on lower level bedroom door and door frame. Missing caulk where tub meets floor in lower level bathroom. Unit D Remove construction covers on smoke detectors.
  2. Dec 2, 2025

    Final - New Construction

    Fails to comply

    InspectorJoe Tomasetti

    See word document for corrections
  3. Jun 26, 2025

    Framing - New Construction

    Fails to comply

    InspectorJoe Tomasetti

    2 X 4 must be nailed @ 2 inch o/c not 4 inch for truss repair .
  4. Mar 31, 2025

    Framing - New Construction

    Partial approval

    InspectorJoe Tomasetti

    Have floor truss company engineer write a repair for broken truss and send to city. Call for inspection Connect and laber radon pipe, 2 X 6 & 2 X 4 studs 16 inch o/c
  5. Mar 31, 2025

    Insulation

    Satisfactory as completed

    InspectorJoe Tomasetti

  6. Feb 24, 2025

    Framing - New Construction

    Fails to comply

    InspectorJoe Tomasetti

    Need plumbing , mechanical and electrical permits and inspections before framing inspection can be completed.