Permit / Minnetonka← Search
#MI283390Mechanical
1584 Oakways, Minnetonka
IssuedJul 9, 2024
StatusUnknown
Value$6,000
Inspections7
Scope of work
Alt/Remodel, 5 supplies, 2 returns, bathfan, and range hood
Location context
Fees & payments
Total fees$200
Inspection record
Inspections7
Passed1
Failed0
- May 13, 2025
Residential Final
APPROVEDInspectorMarshall Lind
Bath fan installed, Insulated & OK
- May 2, 2025
Residential Final
CORRECTION NOTICEInspectorMarshall Lind
1. Need bath fan in laundry room that has a dog washing shower, Talked to contractor on site All other bath fans/kitchen hood supplies & returns OK
- Apr 8, 2025
Residential Final
CORRECTION NOTICEInspectorMarshall Lind
Gas line pressure test 60# OK, Supplies & returns OK, Main floor bath fan & 2 bath fans in master bedroom OK 2 OTHER UPSTAIRS BATH FANS NOT WORKING, CHECK ON FINAL INSPECTION
- Oct 21, 2024
Residential RI
SEE COMMENTSInspectorKyle Peterson
CONTRACTOR SAID CARPENTER WILL FIX RIM THAT WAS CUT UP BY HVAC CONTRACTOR
- Oct 14, 2024
Residential RI
CORRECTION NOTICEInspectorKyle Peterson
CORRECTIONS 1, 2 AND 5 OK
- Sep 16, 2024
Residential RI
CORRECTION NOTICEInspectorKyle Peterson
1. NEED BATH FAN IN OWNERS BATH SHOWER AREA 2. MOVE DUCTS OUT OF EXTERIOR WALLS 3. FIX HEAT RUN ABOVE LAUNDRY ROOM CEILING 4. REROUTE DUCTS OUT OF RIM BOARD 5. BATH FANS NEED R-8 INSULATED VENTING
- Sep 4, 2024
Residential RI
NO SHOWInspectorKyle Peterson
Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.