PULLFIRST[THE RECORD]
Permit / Minnetonka← Search
#MI289563

Mechanical

2400 Royals Dr, Minnetonka

IssuedMar 12, 2025
StatusUnknown
Value$2,422,524
Inspections3
Scope of work

Replace, Hopkins High School 2025 Ventilation Improvements

Location context
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedMar 12, 2025
IssuedMar 12, 2025
Inspection record
Inspections3
Passed3
Failed0
  1. Dec 15, 2025

    Commercial Final

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * Boiler pumps TAB report (OK) **PROVIDE STATE BOILER INSPECTOR'S HYDRO TEST AND FINAL APPROVALS**
  2. Nov 18, 2025

    Commercial Final

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * Boiler piping has been insulated and labeled * Piping supports have been added on roof * One of the 12" mains on roof is leaking glycol * Submit state boiler inspector's verification of hydro test & final approval * Submit balace report
  3. Aug 28, 2025

    Commercial RI

    PARTIAL APPROVAL

    InspectorDale Gronberg

    * This inspection was piggybacked with HVAC inspection. * Comments transferred from other permit

Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.