#MI289654Mechanical
2400 Royals Dr, Minnetonka
IssuedMar 21, 2025
StatusUnknown
Value$1,281,400
Inspections6
Scope of work
Replace, HVAC Remodel - Airside only
Location context
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedMar 18, 2025
IssuedMar 21, 2025
Inspection record
Inspections6
Passed4
Failed0
- Dec 16, 2025
Commercial Final
APPROVEDInspectorDale Gronberg
* TAB received
- Aug 28, 2025
Commercial Final
SEE COMMENTSInspectorDale Gronberg
* Steam piping was demoed and hot water piping installed for new boilers * Piping on roof is 6" welded with insulation and weatherproof jacket * Daily 100 lb.air tests were performed and then insulated due to tight schedule (August 15th deadline) * Looked at tie in connections to new boilers * WALKED ROOF AND LOOKED AT 4,000 FEET OF PIPING. ADD SUPPORTS WHERE NEEDED PER DISCUSSION * SEAL ALL PENETRATIONS. PIPING MUST BE INSULATED THROUGH WALL PENETRATIONS * PIPING INSIDE BOILER ROOMS NOT 100% INSULATED. FINISH INSULATING AND LABEL PIPING * SYSTEM MUST PASS 100 LB. HYDRO TEST FOR STATE BOILER INSPECTOR * RECALL FOR VISUAL INSPECTION ON ITEMS LISTED ABOVE WHEN COMPLETED * SUBMIT BALANCE REPORT
- Aug 27, 2025
Commercial RI
APPROVEDInspectorChris Weaver
SMOKE SHUTDOWN ON BOTH UNITS OK NEED BALANCE REPORT
- Aug 14, 2025
Commercial Final
NOT READYInspectorChris Weaver
- Aug 14, 2025
Commercial RI
PARTIAL APPROVALInspectorChris Weaver
INSTALLATIONS OK WAITING ON NETWORK TO TEST SHUT DOWNS
- Jul 1, 2025
Commercial RI
PARTIAL APPROVALInspectorChris Weaver
---ENSURE ALL BEAM CLAMPS ARE ATTACHED TO TOP CHORD OF TRUSSES VIEWED 2 MECHANICAL ROOMS AROUND AUDITORIUM. OK TO INSULATE UPSTREAM OF VAVS CHANGING TO VAVS VS ZONES. EVERYTHING PRIOR TO VAVS WILL GET EXTERNAL INSULATION, DOWNSTREAM OF VAVS WILL BE INTERNALLY LINED FOR SOUND