Permit / Minnetonka← Search
#MI292904Building
18719 Red Cherry Cir, Minnetonka
IssuedJul 21, 2025
StatusUnknown
Value$437,945
Inspections13
Scope of work
New, Build a new home
Location context
Parcel3111722310027
Coordinates44.89798, -93.51668
Loading map…
199 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedJul 17, 2025
IssuedJul 21, 2025
Inspection record
Inspections13
Passed7
Failed0
- Apr 8, 2026
House Wrap/Lathing
APPROVEDInspectorDan Menth
Lathe for stone ok
- Mar 20, 2026
Residential Footing
PARTIAL APPROVALInspectorBrian Stemwedel
looked at (1) pier footing per plans 48" deep with a 24" bell to support 5' x 5' 'deck' plans (Garage landing- stairs footings) also show another pier footing at base of stair, plans not sealed by engineer and no footing required at stair base if supported on garage slab, none the less, that footing was not dug or inspected
- Mar 5, 2026
House Wrap/Lathing
APPROVEDInspectorChris Weaver
PICS ON SITE
- Mar 4, 2026
House Wrap/Lathing
CORRECTION NOTICEInspectorMarshall Lind
All penetrations must be sealed with flashing tape, No one on site, Phone number given does not go through. Call for re-inspection. Emailed contractor 3/4/26 9:40
- Feb 23, 2026
Residential Framing
APPROVEDInspectorBrian Stemwedel
Framing Corrections from 2/11 made
- Feb 23, 2026
Residential Insulation
PARTIAL APPROVALInspectorBrian Stemwedel
***Does not include lids over Living area ML, Garage. told contractor to take pictures of attic markers and submit certificate at final. DC315 intumescent coating applied over SPF in crawlspace. Insulation approved: Garage walls- FG batt w/ VB ML walls- FG batt w/ VB Basement walls- SPF in rims, SPF over concrete foundation walls, FG batt w/ VB in framed walls
- Feb 11, 2026
Residential Framing
SEE COMMENTSInspectorBrian Stemwedel
1. need to add fasteners (for uplift) at fron roof trusses over front window. 2. Missing (1) anchor bolt in garage w/ in 12" of splice. 3. SPF and Rigid foam installed in crawlspace needs to be protected per R316 -or- provide ES ER report demonstrating compliance w/ out prescriptive thermal/ ignition barrier. verify installation per evaluation report. ***Will take pictures of fasteners at front trusses (low side only) and anchor bolt in garage
- Jan 27, 2026
Foundation/Waterproofing
SEE COMMENTSInspectorBrian Stemwedel
Rigid foam covering ground in crawlspace and SPF exposed on wall needs to be protected [R316.5.4 MRC]. Additionally, at the mechanical RI it was noted that the crawlspace did not have a supply. Crawlspaces need to be ventilated by one of the methods outlined in Section 408 MN Res. Code (usually a supply and passive return)
- Jan 27, 2026
Residential Final
SEE COMMENTSInspectorBrian Stemwedel
Rigid foam covering ground in crawlspace and SPF exposed on wall needs to be protected [R316.5.4 MRC]. Additionally, at the mechanical RI it was noted that the crawlspace did not have a supply. Crawlspaces need to be ventilated by one of the methods outlined in Section 408 MN Res. Code (usually a supply and passive return)
- Nov 10, 2025
Radon
APPROVEDInspectorBrian Stemwedel
reviewed video of proper gas permeable layer covered w/ vb. Stopped by as well and verified VB was sealed as required
- Nov 5, 2025
Radon
CORRECTION NOTICEInspectorBrian Stemwedel
missing Gas Permeable layer, contractor submitted alternate which needs to be reviewed prior to apptoval
- Sep 16, 2025
Residential Footing
APPROVEDInspectorBrian Stemwedel
contractor called and was able to fit in inspection for a 3'x3'x12" footing, in compliance with revised Eng. Note (emailed to C.W. on 9/12 at 9:15 am) also looked at a 15' section of strip footing at front corner of home w/ (2) #4's cont. doweled into ex. footings
- Aug 12, 2025
Meet Contractor
SEE COMMENTSInspectorDan Menth
Met with contractor to review existing foundation after home was demo'd down to foundation, will need engineering on foundation, basement floor has many cracks and signs of settling, slab should be replaced