#MI299249Mechanical
4765 Co Rd No 101, Minnetonka
IssuedDec 11, 2025
StatusUnknown
Value$20,000
Inspections7
Scope of work
Replace, Remodel
Location context
Parcel2911722220012
Coordinates44.91960, -93.50317
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedDec 11, 2025
IssuedDec 11, 2025
Inspection record
Inspections7
Passed4
Failed0
- Jan 23, 2026
Above Ceiling
APPROVEDInspectorBrian Stemwedel
Verified all returns ducted
- Jan 23, 2026
Commercial RI
APPROVEDInspectorBrian Stemwedel
contractor had mechanical systems adjusted with regards to airflows from RTU economizers and MUA unit. had contracor trn on hood to max fan setting. verified operation of MUA with RTU also running. did not appear front door was effected by negative pressure. (easy to open)
- Jan 23, 2026
Commercial Final
APPROVEDInspectorBrian Stemwedel
Per C.W. capture and containment, interlocks compliant. OK to final
- Jan 21, 2026
Commercial Final
CORRECTION NOTICEInspectorChris Weaver
-HOOD IS NOT GETTING ENOUGH MAKE UP AIR FOR HOOD, DOORS TOUGH TO OPEN
- Jan 20, 2026
Commercial Final
NOT READYInspectorChris Weaver
-3 fryers would not innitiate -Need confirmation on capture and containment and RTU functionality
- Jan 14, 2026
Commercial RI
SEE COMMENTSInspectorChris Weaver
WATER TEST, NO LEAKS ECONOMIZER INSTALLED AT 40% 10 FOOT CLEARANCES MET MUST ENSURE RTU/MUA/HOOD ALL COME ON AT THE SAME TIME AND RTU STAYS ON WHEN HOOD IS ON
- Dec 23, 2025
Above Ceiling
APPROVEDInspectorChris Weaver
OK TO INSULATE DUCT SPECIAL INSPECTIONS FORM STILL REQUIRED