Permit / Maple Grove← Search
#MG403249Plumbing
11200 93rd Ave N, Maple Grove
IssuedApr 2, 2025
StatusUnknown
Value$168,600
Inspections7
Scope of work
Remodel, CC2506 Osseo Education Svcs - Warehouse Addition
Location context
Parcel1111922440022
Coordinates45.12366, -93.42389
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedApr 2, 2025
IssuedApr 2, 2025
Inspection record
Inspections7
Passed2
Failed0
- Nov 17, 2025
Final
PassInspectorSteve Lano
- Oct 15, 2025
Rough-In
Partial InspectionInspectorSteve Lano
RPZ tested not yet registered.
- Sep 24, 2025
Final
Partial InspectionInspectorSteve Lano
Need RP's tested and registered for final.
- Sep 24, 2025
Rough-In
PassInspectorSteve Lano
DWV tested and held. Roof drains tested.
- Sep 17, 2025
Rough-In
Not ReadyInspectorSteve Lano
Air test required for DWV
- Sep 17, 2025
Final
Partial InspectionInspectorSteve Lano
Trench drains encased in concrete. Air tests on roof drains OK. Need restraints for roof drain piping. Need airtest for final on DWV and manmeter for sand and flam separators.
- Jul 22, 2025
Rough-In
Partial InspectionInspectorSteve Lano
Ground run piping tested OK. Flood test required for trench drains. Flam tank and sand separator to be tested. Restreaints required for rain leaders 5" piping and larger. Mission couplings to be rated for under ground use.