Permit / Maple Grove← Search
#MG404314Public Works
9800 Fernbrook La N, Maple Grove
IssuedMay 19, 2025
StatusUnknown
Value$846,747
Inspections17
Scope of work
New, Site Utilities
Location context
Parcel1011922220007
Coordinates45.13466, -93.46202
Loading map…
198 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedMay 16, 2025
IssuedMay 19, 2025
Inspection record
Inspections17
Passed0
Failed0
- Aug 7, 2025
S/W Rough In - 5 lb air test req`d on sewer
CancelInspectorSteve Lano
- Aug 6, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Airtest forced mains to structure. Airtest sanitary piping to existing structure backside of building. Sanitary stub into building not holding air. Need manholes Vac tested.
- Aug 5, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm sewer SW sid eof pond to CB for drain tile
- Aug 4, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm sewer west side of building. Testing to follow.
- Aug 1, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm sewer NW side of building. Water test 2
- Jul 31, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Water test 1. Storm water piping Nw side of building.
- Jul 30, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm sewer from Gym area, east west storm next to building
- Jul 22, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Move hydrant back side of building. Storm sewer roof drain from building
- Jul 21, 2025
S/W Rough In - 5 lb air test req`d on sewer
CancelInspectorSteve Lano
Rain
- Jul 17, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Water main, 1 hydrant, 2 stub offs
- Jul 15, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Forced main sewer visual.
- Jul 14, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Need insulation over forced main, not 7.5' of coverage.
- Jul 7, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm from pond
- Jul 3, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm sewer south end of lot.
- Jul 1, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm Sewer from east overflow towards retention pond.
- May 28, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm from retention pond
- May 27, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm parking lot