Permit / Maple Grove← Search
#MG411282Building
18550 70th Way N, Maple Grove
IssuedOct 10, 2025
StatusUnknown
Value$1,900,000
Inspections16
Scope of work
New, New wood framed free-standing restaurant building
Location context
Parcel3011922310103
Coordinates45.08220, -93.51513
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$5,783.3
Total paid$5,783.3
Timeline
ApprovedOct 10, 2025
IssuedOct 10, 2025
Inspection record
Inspections16
Passed8
Failed2
- Mar 24, 2026
Final
PassInspectorRobert Griffin
- Feb 20, 2026
Final
Partial InspectionInspectorRobert Griffin
See TCO for remaining items.
- Feb 3, 2026
Above Ceiling
PassInspectorDylan DeMarais
- Jan 8, 2026
Lath (if required)
Partial InspectionInspectorDylan DeMarais
Lath on south-S.E. walls only, Viewed photos of EIFS application, mortar was applied vertically for drainage.
- Jan 5, 2026
EIFS
Partial InspectionInspectorDJ Hennessey
looked at base coat (Sto Gold Coat) over sheathing. Talked to contractor, he will schedule inspection for lath before stone install and take pictures of each installation layer of StoTherm ci EIFS system.
- Dec 29, 2025
Insulation
PassInspectorDJ Hennessey
- Dec 22, 2025
Sheathing
PassInspectorDylan DeMarais
- Dec 22, 2025
Framing 60
PassInspectorDylan DeMarais
- Dec 19, 2025
Insulation
Not ReadyInspectorRobert Griffin
- Dec 16, 2025
Framing 60
Correction noticeInspectorDylan DeMarais
- Nov 12, 2025
Poured Floor
PassInspectorColby Cartney
- Nov 10, 2025
Underslab Vapor Barrier
Correction noticeInspectorDylan DeMarais
Re-inspection needed after first pour of floor at cooler/freezer area slab.
- Nov 3, 2025
Foundation-Exterior
PassInspectorDJ Hennessey
- Oct 28, 2025
Poured Wall
PassInspectorKen Nelson
- Oct 24, 2025
Poured Wall
FailedInspectorJason Bredenberg
Need more info from engineer on Pier dowels, rebar needs to be tied, piers are to close to inner wall, engineer to address.
- Oct 15, 2025
Footing
FailedInspectorDylan DeMarais
Concrete was wrong PSI, 4000 PSI is required per engineering, 3000 PSI was delivered. Engineer to sign off on the mix used and for using epoxy for pier dowels instead of hook dowels. UPDATE - ENGINEER OKAYED THE 3000PSI, DID NOT APPROVE EPOXY FOR PIER DOWELS. MUST OPEN PADS TO INSTALL HOOK DOWELS PER ENGINEERS DETAIL DATED 10/16/25.