Permit / Maple Grove← Search
#MG414323Public Works
18550 70th Way N, Maple Grove
IssuedOct 23, 2025
StatusUnknown
Value$59,000
Inspections10
Scope of work
New, Install new 4'' sanitary sewer 3 manholes. Install new 6'' water main and relocate hydrant
Location context
Parcel3011922310103
Coordinates45.08220, -93.51513
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$20
Total paid$20
Timeline
ApprovedOct 23, 2025
IssuedOct 23, 2025
Inspection record
Inspections10
Passed1
Failed0
- Mar 2, 2026
Sewer & Water Final
PassInspectorSteve Lano
- Nov 12, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Air test sanitary from grease interceptor to man hole. Vacc test manhole.
- Nov 10, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Vacc test grease trap 5" water column no drop.
- Nov 6, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorAndrew Rogalski
Bug Test 2
- Nov 5, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Bug test 1, sanitary sewer install to cleanout.
- Nov 4, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Storm sewer repair in HDPE
- Oct 31, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Hydro test water piping 207psi for 2 hr.
- Oct 30, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Plastic pipe to be bedded in sand 1' above pipe.
- Oct 29, 2025
S/W Rough In - 5 lb air test req`d on sewer
Partial InspectionInspectorSteve Lano
Water piping hydrant and main to front of building.
- Oct 28, 2025
S/W Rough In - 5 lb air test req`d on sewer
CancelInspectorSteve Lano
rain
Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.