#ED213199

Building

10 Southdale Ctr 1800, Edina

IssuedOct 14, 2024
StatusUnknown
Value$801,633
Inspections13
Scope of work

Alteration/Remodel, tenant buildout including new storefront, interior walls and finishes

Location context
Fees & payments
Total fees$3,500
Total paid$3,500
Timeline
ApprovedOct 11, 2024
IssuedOct 14, 2024
Inspection record
Inspections13
Passed10
Failed0
  1. Jun 6, 2025

    Building Final - COMMERCIAL

    Approved

    InspectorTedd Nelson

  2. May 7, 2025

    Fire Dept final

    Approved, w/ Comments

    InspectorBrian Hanrahan

    -smoke exhaust tested good by Summit. -Fire alarm good. WIll sync with addition of power supplies
  3. Feb 12, 2025

    Bldg Progress

    Progress Report

    InspectorTedd Nelson

    - Met with Troy Williams 763-257-7355 (Elder Jones) contractor and Matt Smith from Summit doing the pre-test for the smoke control...Dampers were not activating
  4. Jan 31, 2025

    Smoke Control

    Approved

    InspectorJim G Meyer

    framing of fire damper in space saw framing around it and also the cut sheet on what needed to be done
  5. Jan 31, 2025

    Building Final - COMMERCIAL

    Not Approved

    InspectorRick Chase

    Framing for the two fire dampers failed, Framed to only allow two sides of the retaining angles. Called Paul Ayres and provided Kimball pauls email and phone number to come up with a code compliant solution. Mechanical permit 214315 final required - Install two dampers for the EVAC and finish installing duct work - Provide a final test report from Summit on the post secondary smoke control
  6. Jan 29, 2025

    Building Final - COMMERCIAL

    Not Approved

    InspectorTedd Nelson

    - Mechanical permit 214315 final required - Install two dampers for the EVAC and finish installing duct work - Provide a final test report from Summit on the smoke evac
  7. Jan 28, 2025

    Fire Dept final

    Partial Approval w/ Comments

    InspectorBrian Hanrahan

    -tape removed from sprinkler head -FA function test will be done under FA permit
  8. Jan 27, 2025

    Building Final - COMMERCIAL

    Not Approved

    InspectorTedd Nelson

    - Electrical final required - Mechanical permit 214315 final required - Install accessible fitting room signage - Remove thumb turns and install verbiage to REMAIN UNLOCKED - Need to install glass for both store front doors - Install two dampers for the EVAC and finish installing duct work - Provide a final test report from Summit on the post secondary smoke control
  9. Jan 23, 2025

    Building Final - COMMERCIAL

    Partial Approval

    InspectorPeter Akmenkalns

    need electrical final and smoke comtroll report from aires mech.(dampers to be installed)
  10. Dec 20, 2024

    Fire Dept final

    Progress Report

    InspectorBrian Hanrahan

    -tape on sprinkler head above bathroom
  11. Nov 25, 2024

    Fire Sprinkler Final (For appt: 952-826-0339)

    Approved

    InspectorBrian Hanrahan

  12. Nov 19, 2024

    Framing-Commercial

    Partial Approval

    InspectorPeter Akmenkalns

    all framing except store front will all when finished
  13. Nov 7, 2024

    Bldg Progress

    Appointment

    InspectorPeter Akmenkalns

    met on site to discuss how inspections will work for space