#ED213199Building
10 Southdale Ctr 1800, Edina
IssuedOct 14, 2024
StatusUnknown
Value$801,633
Inspections13
Scope of work
Alteration/Remodel, tenant buildout including new storefront, interior walls and finishes
Location context
Fees & payments
Total fees$3,500
Total paid$3,500
Timeline
ApprovedOct 11, 2024
IssuedOct 14, 2024
Inspection record
Inspections13
Passed10
Failed0
- Jun 6, 2025
Building Final - COMMERCIAL
ApprovedInspectorTedd Nelson
- May 7, 2025
Fire Dept final
Approved, w/ CommentsInspectorBrian Hanrahan
-smoke exhaust tested good by Summit. -Fire alarm good. WIll sync with addition of power supplies
- Feb 12, 2025
Bldg Progress
Progress ReportInspectorTedd Nelson
- Met with Troy Williams 763-257-7355 (Elder Jones) contractor and Matt Smith from Summit doing the pre-test for the smoke control...Dampers were not activating
- Jan 31, 2025
Smoke Control
ApprovedInspectorJim G Meyer
framing of fire damper in space saw framing around it and also the cut sheet on what needed to be done
- Jan 31, 2025
Building Final - COMMERCIAL
Not ApprovedInspectorRick Chase
Framing for the two fire dampers failed, Framed to only allow two sides of the retaining angles. Called Paul Ayres and provided Kimball pauls email and phone number to come up with a code compliant solution. Mechanical permit 214315 final required - Install two dampers for the EVAC and finish installing duct work - Provide a final test report from Summit on the post secondary smoke control
- Jan 29, 2025
Building Final - COMMERCIAL
Not ApprovedInspectorTedd Nelson
- Mechanical permit 214315 final required - Install two dampers for the EVAC and finish installing duct work - Provide a final test report from Summit on the smoke evac
- Jan 28, 2025
Fire Dept final
Partial Approval w/ CommentsInspectorBrian Hanrahan
-tape removed from sprinkler head -FA function test will be done under FA permit
- Jan 27, 2025
Building Final - COMMERCIAL
Not ApprovedInspectorTedd Nelson
- Electrical final required - Mechanical permit 214315 final required - Install accessible fitting room signage - Remove thumb turns and install verbiage to REMAIN UNLOCKED - Need to install glass for both store front doors - Install two dampers for the EVAC and finish installing duct work - Provide a final test report from Summit on the post secondary smoke control
- Jan 23, 2025
Building Final - COMMERCIAL
Partial ApprovalInspectorPeter Akmenkalns
need electrical final and smoke comtroll report from aires mech.(dampers to be installed)
- Dec 20, 2024
Fire Dept final
Progress ReportInspectorBrian Hanrahan
-tape on sprinkler head above bathroom
- Nov 25, 2024
Fire Sprinkler Final (For appt: 952-826-0339)
ApprovedInspectorBrian Hanrahan
- Nov 19, 2024
Framing-Commercial
Partial ApprovalInspectorPeter Akmenkalns
all framing except store front will all when finished
- Nov 7, 2024
Bldg Progress
AppointmentInspectorPeter Akmenkalns
met on site to discuss how inspections will work for space