#ED221946

Building

10 Southdale Ctr 1310a, Edina

IssuedJul 11, 2025
StatusUnknown
Value$1,105,836
Inspections12
Scope of work

Alteration/Remodel, Interior Remodel of an existing suite at Southdale Mall including associated Arch and MEP work.

Location context
Fees & payments
Total fees$2,000
Total paid$2,000
Timeline
ApprovedJul 11, 2025
IssuedJul 11, 2025
Inspection record
Inspections12
Passed10
Failed0
  1. Nov 12, 2025

    Building Final - COMMERCIAL

    Approved

    InspectorTedd Nelson

  2. Nov 12, 2025

    Smoke Control

    Partial Approval w/ Comments

    InspectorBrian Hanrahan

    -smoke control report added
  3. Nov 3, 2025

    Building Final - COMMERCIAL

    Partial Approval

    InspectorTedd Nelson

    - Mechanical permit 223275 and Plumbing permit 223276 final required
  4. Oct 28, 2025

    Building Final - COMMERCIAL

    Not Approved

    InspectorTedd Nelson

    - Mechanical and Plumbing final required. - Lower breakroom sink to =<34" AFF - Remove thumb turns and add signage to the front doors
  5. Oct 28, 2025

    Bldg Progress

    Progress Report

    InspectorTedd Nelson

    - A separate permit is required for assembly spaces A111, B103, and C102
  6. Oct 23, 2025

    Fire Sprinkler Final (For appt: 952-826-0339)

    Approved

    InspectorBrian Hanrahan

  7. Oct 22, 2025

    Fire Sprinkler Rough-In (add`l permit req`d)

    Approved

    InspectorBrian Hanrahan

  8. Oct 21, 2025

    Smoke Control

    Not Approved

    InspectorBrian Hanrahan

    -smoke control did not work. Fans didn't turn on
  9. Sep 8, 2025

    Above Ceiling Grid

    Approved

    InspectorTedd Nelson

    - Fire and electrical inspection before covering
  10. Sep 8, 2025

    Framing-Commercial

    Approved

    InspectorTedd Nelson

    - Structural store front installed - Verify accessible restroom clearances - Provide 90 min door frames at rear and side rated cores
  11. Aug 14, 2025

    Framing-Commercial

    Partial Approval

    InspectorPeter Akmenkalns

    need glass front walls and front foyer area
  12. Jul 31, 2025

    Bldg Progress

    Progress Report

    InspectorTedd Nelson

    - Walk the space with Dustin from CoBeck - Will need to maintain the 2hr corridor and verify the continuity of the gyp.