PULLFIRST[THE RECORD]
Permit / Apple Valley← Search
#AV129168

Mechanical

7534 149th St W, Apple Valley

IssuedSep 26, 2024
StatusUnknown
Value$54,500
Inspections8
Scope of work

Miscellaneous, Install Owner Provided MUA/Fan and Hood. F/I RTU’s, Exhaust Fan, Ductwork, Insulation, Grilles.

Location context
Parcel014490001040
Coordinates44.73335, -93.21938
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$244.18
Total paid$244.18
Timeline
ApprovedSep 26, 2024
IssuedSep 26, 2024
Inspection record
Inspections8
Passed3
Failed0
  1. Oct 22, 2024

    Final

    Compliant

    InspectorChris Pequin

    Final balance report recieved
  2. Oct 21, 2024

    Final

    Partial Pass

    InspectorChris Pequin

    Final RTU hook ups OK. Missing balance report.
  3. Oct 17, 2024

    Rough In

    Compliant

    InspectorChris Pequin

  4. Oct 17, 2024

    Miscellaneous

    Compliant

    InspectorChris Pequin

  5. Oct 17, 2024

    Final

    Partial Pass

    InspectorChris Pequin

    Smoke test of captivaire unit. Smoke control shut offs tested. Only need to inspect final connections to RTUs and receive final balance report.
  6. Oct 14, 2024

    Above Ceiling

    Compliant

    InspectorChris Pequin

    Flexes and diffusers
  7. Oct 3, 2024

    Rough In

    Partial Pass

    InspectorChris Pequin

    Light test passes. Last saddles and roof penetrations inspected. Still need to inspect gas line rough in and air test and RTUs on roof.
  8. Oct 1, 2024

    Rough In

    Non-Compliant

    InspectorChris Pequin

    Light test failed at captivaire unit at 4th coupling up from hood facing front entry. Otherwise rough in passed prior to flexes and diffusers.

Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.