#AV132787Building
6175 147th St W, Apple Valley
IssuedMay 13, 2025
StatusUnknown
Value$2,000,000
Inspections5
Scope of work
Tenant Improvement, Interior alteration inside existing building
Location context
Fees & payments
Total fees$3,000
Total paid$3,000
Timeline
ApprovedMay 12, 2025
IssuedMay 13, 2025
Inspection record
Inspections5
Passed0
Failed1
- Oct 28, 2025
Final - 30 minutes
CompliantInspectorChris Andrejka
- Oct 16, 2025
Final - 30 minutes
Non-CompliantInspectorChris Andrejka
all corrections from 10/13 have been addressed. the racking permit must be issued and closed out prior to CO. fire alarm permit still open.
- Oct 13, 2025
Final - 30 minutes
Non-CompliantInspectorChris Andrejka
missing vertical grab bars in restrooms. the accessible restroom next to the janitor closet must have the within 16-18" of the side wall. hvac correction any mechanical equipment that is within 10' of the roof edge requires a guard 42" min in height and must extend 30" past either side of the equipment the guard is serving. Also, missing balance report. plumbing correction not seen Temp and pressure relief valve not installed on water heater.
- Sep 8, 2025
Final - 30 minutes
FailInspectorGeorge Dorn
This comment is for plumbing final. Temp and pressure relief valve not installed on water heater, check at final. I did not do a building final, that needs to be done yet.
- Jul 23, 2025
Framing - 30 minutes
CompliantInspectorChris Andrejka