PULLFIRST[THE RECORD]
Permit / Apple Valley← Search
#AV136246

Plumbing

15690 English Ave, Apple Valley

IssuedAug 11, 2025
StatusUnknown
Value$156,000
Inspections16
Scope of work

Fixtures, Plumbing

Location context
Parcel015589101020
Coordinates44.71927, -93.17889
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$659.24
Total paid$659.24
Timeline
ApprovedAug 11, 2025
IssuedAug 11, 2025
Inspection record
Inspections16
Passed2
Failed0
  1. Feb 9, 2026·7:30 AM - 8:00 AM

    Backflow Test Report Received, Final

    scheduled

    InspectorChris Pequin

  2. Feb 6, 2026

    Final

    Compliant

    InspectorChris Pequin

  3. Feb 6, 2026

    Backflow Test Report Received

    Compliant

    InspectorChris Pequin

  4. Jan 28, 2026

    Backflow Test Report Received

    Partial Pass

    InspectorChris Pequin

    2 RPZ tests received for S#s 82201 & NSF-61-G Still need DCV for fire suppression
  5. Jan 23, 2026

    Backflow Test Report Received

    Non-Compliant

    InspectorChris Pequin

    Two backflow test reports received. Both models indicated are RPs and the PSIDs do not meet the requirements of the ASSE 5000 Field Test Procedure. Valves must be retested. Missing report for fire suppression DCV as well.
  6. Jan 23, 2026

    Rough In

    Compliant

    InspectorChris Pequin

  7. Jan 20, 2026

    Final

    Non-Compliant

    InspectorChris Pequin

    Need backflow test results
  8. Jan 20, 2026

    Miscellaneous

    Compliant

    InspectorChris Pequin

    PRV not required. PSI verified to be 62 PSI
  9. Jan 13, 2026

    Miscellaneous

    Non-Compliant

    InspectorPatrick Devery

    The approved plans show a pressure reducing valve at domestic water, but none present. Unsure if this is required in this location.
  10. Jan 13, 2026

    Backflow Test Report Received

    Not Ready

    InspectorPatrick Devery

    Both testable devices not tested.
  11. Jan 13, 2026

    Final

    Not Ready

    InspectorPatrick Devery

    T&P valve from water heater is required to be piped separately to indirect drain (opposed to disaster pan). Backflow devices not tested. Disaster pan and T&P valve not completely plumbed to mop sink below. Sink at tire washing station does not have trap arm tied to drain and vent.
  12. Jan 13, 2026

    Manometer

    Compliant

    InspectorPatrick Devery

  13. Oct 30, 2025

    Air Test

    Compliant

    InspectorChris Pequin

    Gas piping at #55. RI of gas piping complete other than on roof. Add hanger to one radiant heater at end by appliance.
  14. Oct 20, 2025

    Rough In

    Partial Pass

    InspectorChris Pequin

    Sales center rough in and 5# air only. Need to verify final VTR diameter later (currently only 3"). Trap primer must go.
  15. Sep 17, 2025

    Underground

    Compliant

    InspectorChris Pequin

    Underground and #5 air on underground
  16. Sep 2, 2025

    Underground

    Non-Compliant

    InspectorChris Pequin

    Missing 2 clean outs at grids B5 and A8. Revised plans required for tire wash since underground elevation too low for catch basin. Missing drain for drinking fountain. Submit revised plumbing plans for sewer connection at interceptor.

Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.