Permit / Apple Valley← Search
#AV136246Plumbing
15690 English Ave, Apple Valley
IssuedAug 11, 2025
StatusUnknown
Value$156,000
Inspections16
Scope of work
Fixtures, Plumbing
Location context
Parcel015589101020
Coordinates44.71927, -93.17889
Loading map…
200 nearby
This permitNearby
Fees & payments
Total fees$659.24
Total paid$659.24
Timeline
ApprovedAug 11, 2025
IssuedAug 11, 2025
Inspection record
Inspections16
Passed2
Failed0
- Feb 9, 2026·7:30 AM - 8:00 AM
Backflow Test Report Received, Final
scheduledInspectorChris Pequin
- Feb 6, 2026
Final
CompliantInspectorChris Pequin
- Feb 6, 2026
Backflow Test Report Received
CompliantInspectorChris Pequin
- Jan 28, 2026
Backflow Test Report Received
Partial PassInspectorChris Pequin
2 RPZ tests received for S#s 82201 & NSF-61-G Still need DCV for fire suppression
- Jan 23, 2026
Backflow Test Report Received
Non-CompliantInspectorChris Pequin
Two backflow test reports received. Both models indicated are RPs and the PSIDs do not meet the requirements of the ASSE 5000 Field Test Procedure. Valves must be retested. Missing report for fire suppression DCV as well.
- Jan 23, 2026
Rough In
CompliantInspectorChris Pequin
- Jan 20, 2026
Final
Non-CompliantInspectorChris Pequin
Need backflow test results
- Jan 20, 2026
Miscellaneous
CompliantInspectorChris Pequin
PRV not required. PSI verified to be 62 PSI
- Jan 13, 2026
Miscellaneous
Non-CompliantInspectorPatrick Devery
The approved plans show a pressure reducing valve at domestic water, but none present. Unsure if this is required in this location.
- Jan 13, 2026
Backflow Test Report Received
Not ReadyInspectorPatrick Devery
Both testable devices not tested.
- Jan 13, 2026
Final
Not ReadyInspectorPatrick Devery
T&P valve from water heater is required to be piped separately to indirect drain (opposed to disaster pan). Backflow devices not tested. Disaster pan and T&P valve not completely plumbed to mop sink below. Sink at tire washing station does not have trap arm tied to drain and vent.
- Jan 13, 2026
Manometer
CompliantInspectorPatrick Devery
- Oct 30, 2025
Air Test
CompliantInspectorChris Pequin
Gas piping at #55. RI of gas piping complete other than on roof. Add hanger to one radiant heater at end by appliance.
- Oct 20, 2025
Rough In
Partial PassInspectorChris Pequin
Sales center rough in and 5# air only. Need to verify final VTR diameter later (currently only 3"). Trap primer must go.
- Sep 17, 2025
Underground
CompliantInspectorChris Pequin
Underground and #5 air on underground
- Sep 2, 2025
Underground
Non-CompliantInspectorChris Pequin
Missing 2 clean outs at grids B5 and A8. Revised plans required for tire wash since underground elevation too low for catch basin. Missing drain for drinking fountain. Submit revised plumbing plans for sewer connection at interceptor.
Data sourced from Minnesota Department of Labor & Industry, Minnesota Attorney General, federal OSHA, and municipal permit offices. Records are public and may not reflect pending appeals or corrections.