BECKER SWITCHING STATION, BECKER, MN 55308
Standard 19260954 F
ELECTRIC SHOCK AND FALL - CONTACT WITH INDUCED VOLTAGE
AN EMPLOYEE WAS WORKING AT A HEIGHT OF 18 FEET ABOVE THE GROUND ALIGNING SWITCHE S. HE CONTACTED A DEENERGIZED LINE THAT HAD INDUCED VOLTAGE ON IT. (THE LINE WAS INADEQUATELY GROUNDED.) THE EMPLOYEE FROZE TO THE LINE TEMPORARILY, THEN DROPPE D TOWARDS THE GROUND. DURING THE FALL, HIS LEG WEDGED IN A TRANSFORMER SUPPORT. THIS STOPPED HIS FALL SHORT OF THE GROUND. THE EMPLOYEE SUFFERED A BROKEN BIG TO E, A SPRAINED ANKLE, AND A SEPARATED PELVIS.