Mar 31, 2026·375 WATER ST WLikely
Electrical Commercial Repair/Alter · Saint Paul · Permit DSIELEC-031102-2026
Electrical work included correcting multiple panel and feeder deficiencies to achieve NEC compliance. This involved installing proper breaker blanks, knockout seals, reducing washers, and a dead front sealing assembly, as well as removing improper openings and non-compliant fittings. Existing feeder conductors were removed and reinstalled after replacing damaged conduit, couplings, and liquidtight connectors, with all terminations completed using anti-oxidation compound. A new junction box with proper connectors was installed to ensure conductors are protected from physical damage, followed by general cleanup and testing of all connections.